Plan Review Notes
Plan Review Notes For Permit 19010113
Permit Number 19010113
Review Stop P
Sequence Number 3
Notes
Date Text
2019-05-14 15:47:28PLUMBIG 3RD REVIEW**DENIED**
  
 1) ANSWERED**
  
 2) NOT FULLY ANSWERED. PROVIDE COMPLETE INSTALLATION
 MANUAL SHOWING THE E.F RATING IS .92 AND MATCHES THE
 R405-2017 FORM. YOU SUBMITTED SPEC FOR AN ECO 27
 TANKLESS WATER HEATER REQUIRES (3) 40AMP BREAKERS BUT
 ELC SHEET SHOWS ON (1) 50AMP BREAKER. PLEASE CLARIFY.
 OLD NOTE:PROVIDE TANKLESS WATER HEATER MANUFACTURES
 INSTALLATION MANUAL, SHOW WITH THE CORRECT HEAT RISE IT
 WILL BE ABLE TO SUPPLY HOT WATER AS REQUIRED FBC-P
 607.1 WHILE AT FULL DEMAND FBC-P 604.3 TO ALL FIXTURES.
  
 3) ANSWERED**
  
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703