Plan Review Notes
Plan Review Notes For Permit 19010113
Permit Number 19010113
Review Stop P
Sequence Number 2
Notes
Date Text
2019-04-08 10:30:07PLUMBIG 2ND REVIEW**DENIED** PROVISO APPROVAL (1-SET)
 OF THE SHEETS FROM 1ST REVIEW HAVE BEEN REMOVED**
  
 1) PROVIDE A PLUMBING SANITARY ISOMETRIC DRAWING. FBC
 107.3.5
  
 2) PROVIDE TANKLESS WATER HEATER MANUFACTURES
 INSTALLATION MANUAL, SHOW WITH THE CORRECT HEAT RISE IT
 WILL BE ABLE TO SUPPLY HOT WATER AS REQUIRED FBC-P
 607.1 WHILE AT FULL DEMAND FBC-P 604.3 TO ALL FIXTURES.
  
 3) R405-2017 FORM HAS WRONG ADDRESS AND WRONG WATER
 HEATER LISTED. PROVIDE CORRECT TANKLESS AND REMOVE
 40GAL STORAGE TANK. FBC 107.3.5
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  
  
  
  