| Plan Review Notes For Permit 19010113 |
| Permit Number |
19010113 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-04-08 10:30:07 | PLUMBIG 2ND REVIEW**DENIED** PROVISO APPROVAL (1-SET) | | | OF THE SHEETS FROM 1ST REVIEW HAVE BEEN REMOVED** | | | | | | 1) PROVIDE A PLUMBING SANITARY ISOMETRIC DRAWING. FBC | | | 107.3.5 | | | | | | 2) PROVIDE TANKLESS WATER HEATER MANUFACTURES | | | INSTALLATION MANUAL, SHOW WITH THE CORRECT HEAT RISE IT | | | WILL BE ABLE TO SUPPLY HOT WATER AS REQUIRED FBC-P | | | 607.1 WHILE AT FULL DEMAND FBC-P 604.3 TO ALL FIXTURES. | | | | | | 3) R405-2017 FORM HAS WRONG ADDRESS AND WRONG WATER | | | HEATER LISTED. PROVIDE CORRECT TANKLESS AND REMOVE | | | 40GAL STORAGE TANK. FBC 107.3.5 | | | | | | TIM HUNT | | | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR | | | CITY OF WEST PALM BEACH | | | 561-248-2703 | | | [email protected] | | | [email protected] | | | | | | | | | | | | | | | |
|