2019-04-05 17:18:27RESIDENTIAL (R3)ALTERATION/ADDITION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT;
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. 1106 FBC-EXISTING BUILDING AND SEC. R101.4.2
 AND R101.5 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REVISE ENERGY CALCULATIONS SUBMITTED:
 A) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM:
 (1) THE ADDRESS IS 300 LYTLE ST. NOT 301 LYTLE ST.
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
 (2) PROVIDE THE OWNER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
 (3) PROVIDE THE BUILDER'S NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 B) ITEM # 1 ON PAGE 1 OF 5 IS INCORRECT. THIS IS NOT
 NEW CONSTRUCTION. THE HOUSE IS EXISTING. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) ITEM #4 ON PAGE 1 OF 5 IS INCORRECT. ACCORDING TO
 PLANS SUBMITTED, THERE ARE 3 BEDROOMS NOT 4. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) ITEM #6 ON PAGE 1 OF 5 IS INCORRECT. CONDITIONED
 FLOOR AREA DOESN'T MATCH PLANS. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E) IT LOOKS LIKE PERSON PREPARING THE ENERGY
 CALCULATIONS IS DOING THE CALCULATIONS FOR THE ENTIRE
 HOUSE. PROVIDE WINDOWS AND DOORS MANUFACTURER'S
 SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7 ON PAGE
 1 OF 5 FOR ALL EXISTING AND NEW WINDOWS/DOORS AS
 REQUIRED BY SEC. R405.4.3 FBC-ENERGY CONSERVATION.
  
 F) ITEM #8 ON PAGE 1 OF 5 IS INCORRECT. SLAB ON GRADE
 AREA DOESN'T DOESN'T MATCH PLANS. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) ITEM #9(B) ON PAGE 1 OF 5 IS INCORRECT. THERE IS NOT
 ADJACENT WALL. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 H) ITEM #11, 12 AND 13 ON PAGE 1 OF 5 ARE INCORRECT.
 SEE PLANS FOR NUMBER OF A/C UNITS AND REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 I) PROVIDE THE NAME OF PERSON PERFORMING THE ANALYSIS
 AND GENERATING THE REPORT AS REQUIRED BY SEC.
 R405.4.2.1 FBC- ENERGY CONSERVATION.
  
 J) OWNER TO COMPLETE CERTIFICATION AT BOTTOM OF FORM.
 INCLUDE THE DATE WHEN CERTIFYING THAT THE BUILDING IS
 IN COMPLIANCE WITH THE CODE. SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 K) PROJECT INFORMATION ON PAGE 2 OF 5 IS INCORRECT.
 THERE ARE NOT 2 STORIES IN THIS HOUSE. SEE PLANS AND
 REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 L) SPACES INFORMATION ON PAGE 2 OF 5 IS INCORRECT. SEE
 SPACES AND NUMBER OF KITCHENS ON PLANS AND REVISE AS
 REQUIRED. ALSO, PROVIDE CORRECT NUMBER OF OCCUPANTS
 BASED ON THE NUMBER OF BEDROOMS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 M) WALLS AND WINDOWS INFORMATION ON PAGE 3 OF 5 IS
 INCORRECT. SEE PLANS AND REVISE AS REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 ORIGINAL COMMENT:
 2- INFORMATION ON SHEET 02 FOR PROPOSED ROOF FRAMING
 PLAN IS NOT CLEAR. SEC. 107.2.1 CITY AMENDMENTS.
 A) CLEARLY SPECIFY WHAT AT ARE THE EXISTING AND
 PROPOSED ROOF FRAMING MEMBERS. CLEARLY SPECIFY SIZES OF
 ALL ROOF FRAMING MEMBERS. CLEARLY SPECIFY ALL END
 CONNECTIONS OF THE ROOF FRAMING MEMBERS.
  
 RESPONSE:
 PARTIALLY COMPLIED. NEW ROOF TRUSS SYSTEM WAS PROVIDED.
 BUT NEED TO CLARIFY THE FOLLOWING:
 (1) HOW IS THE PROPOSED TRUSS CONNECTOR "A" (SIMPSON
 HETA20) GOING TO BE INSTALLED. THIS CONNECTOR NEEDS 4"
 EMBEDMENT. HOW DO YOU GET THE 4" EMBEDMENT IN AN
 EXISTING CONCRETE BEAM?. SEC. 107.2.1 CITY AMENDMENTS.
  
 (2) HOW IS THE PROPOSED TRUSS CONNECTOR "B" (SIMPSON
 H10A) GOING TO BE INSTALLED. THIS IS A WOOD TO WOOD
 CONNECTOR. ACCORDING TO PLANS SUBMITTED, IT LOOKS LIKE
 THERE IS A CONCRETE TIE BEAM NOT WOOD BEAM. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B)OK. NEW ROOF TRUSS SYSTEM.
  
 C) OK. NO STEEL COLUMNS/BEAMS
  
 3- OK.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 ORIGINAL COMMENT:
 A) NEW EXTERIOR DOORS SHOWN ON PLANS.
  
 RESPONSE:
 DRAWINGS SUBMITTED WITH FLORIDA PRODUCT APPROVAL
 FL22513-R2 IS FOR SOLID DOORS ONLY. PLANS SHOW DOOR
 WITH GLAZING. PROVIDE PRODUCT APPROVAL FOR DOOR WITH
 GLAZING AS SHOWN ON PLANS.
  
 ORIGINAL COMMENT:
 B)WINDOW MULLIONS AS SHOWN ON PLANS. AND REQUIRED:
 CLEARLY SPECIFY MULLION SIZE TO BE USED TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENT BASED ON DOOR PRODUCT APPROVAL SUBMITTED.
 C) SHUTTERS IF DOOR WITH GLAZING DON'T HAVE IMPACT
 GLASS. AND, PROVIDE COMPLETE SHUTTERS INSTALLATION
 SCHEDULE.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 ORIGINAL COMMENT:
 6- PLANS NEED TO SPECIFY INSULATION IN THE GARAGE AREA
 THAT IS GOING TO BE CONVERTED TO BEDROOM. WALLS AND
 CEILING. SEC. R103.2 FBC-ENERGY CONSERVATION. NOTE:
 ENERGY CALCULATIONS AND PLANS TO BE COORDINATED TO
 AVOID CONFLICTS/DELAYS.
  
 RESPONSE:
 PLANS DON'T SPECIFY INSULATION AT THE PERIMETER WALL OF
 THE EXISTING GARAGE AREA TO BE CONVERTED TO BEDROOM.
  
 NEW COMMENTS:
 7- WINDOWS IN MASTER BEDROOM WERE REVISED. WINDOWS IN
 MASTER BEDROOM SHOWN ON PREVIOUS SUBMITTAL USED TO
 COMPLY WITH EGRESS. NOW WINDOWS IN THIS BEDROOM DON'T
 SEEM TO COMPLY WITH THE EGRESS REQUIREMENTS OF SEC.
 R310.2.1 FBC-RESIDENTIAL. SHOW COMPLIANCE WITH THE
 EGRESS REQUIREMENTS.
  
 8- COMPLETE NEW ROOF SYSTEM IS PROPOSED. SHOW LOCATION
 AND SIZE OF ATTIC ACCESS SHOWING COMPLIANCE WITH SEC.
 R807 FBC-RESIDENTIAL.
  
 9- PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR
 REVISED MATERIALS MAY RESULT IN NEW PLAN REVIEW
 COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS. SUBMIT OLD DRAWINGS
 FOR REFERENCE.
  
  