| Notes |
| Date |
Text |
| 2019-01-24 14:42:45 | APPROVED | | | PROVISO | | | | | | 1. RE: TANK-LESS WATER HEATER; SUBMIT MANUFACTURER'S | | | SPECIFICATION SHEET TO INCLUDE THE MODEL NUMBER, GPM | | | AND ELECTRICAL CHARACTERISTICS FOR THE TANKLESS WATER | | | HEATERS PER WPB FBC 107.2.1 AND CONFIRM THEY WILL | | | SUPPLY THE HOT WATER DEMAND. SAID SPECIFICATION MAY BE | | | SUBMITTED AS A DEFERRED SUBMITTAL AS DEFINED BY WPB FBC | | | 107.3.4.1 AND SHALL BE SUBMITTED, APPROVED AND IN PLACE | | | PRIOR TO THE FIRST PLUMBING INSPECTION. | | | 2. RE: PLAN SHEET 01: PLUMBING RISER; SEE REDLINED | | | ITEMS ON DRAWING TO COMPLY WITH FBC RES SECTION 3108 | | | 3. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S | | | APPROVAL |
|