2019-02-04 10:11:082017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19010093
 ADD: 2235 OKEECHOBEE BLVD.
 CONT: HODGEN CONSTRUCTION, LLC
 TEL: 954-727-0333
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. FEB. 04/2019
 ACTION: DENIED
  
 1) PROJECT COVER SHEET G001:
 1A) APPLICABLE CODES, PLEASE UPDATE THE AMENDMENTS
 CHAPTER 1FROM THE 2010 FLORIDA BUILDING CODE TO THE
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, 6TH EDITION (2017) CHAPTER 1, ADMINISTRATION.
  
 1B) APPLICABLE CODES, PLEASE UPDATE THE FLORIDA
 BUILDING CODE 5TH EDITION (2014) TO THE 6TH EDITION OF
 THE FLORIDA BUILDING CODE (2017). THIS CODE WAS ADOPTED
 STATEWIDE ON DEC. 31/ 2017.
  
 1C) SPECIAL INSPECTION SUMMARY INDICATES THE USE OF THE
 IBC AS THE CODE THESE PLANS WERE DEVELOPED UNDER.
 PLEASE NOTE IN THE 2017 FBC-B SECTIONS 1704 & 1705
 WHICH DEAL WITH TEST AND INSPECTIONS IS RESERVED. THE
 TERM SPECIAL INSPECTORS IS A TERM USED IN CONJUNCTION
 WITH THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
 NOT APPLICABLE TO THIS PROJECT.
  
 1D)(1) THE COVERSHEET DOES NOT INDICATE WHAT THE
 MINIMUM BUILDING TYPE OF CONSTRUCTION IS? THE PLANS DO
 NOT PROVIDE THE SQUARE FOOT AREA, IF THERE WAS AREA
 INCREASES TAKEN FRONTAGE AND OR FIRE SPRINKLERS. THE
 SUBMITTED PLAN DOES NOT INCLUDE FIRE SPRINKLER PLANS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE SECTION 503).
 BUILDING AREA INCLUDES: AREAS OF THE BUILDING NOT
 PROVIDED WITH SURROUNDING WALLS SHALL BE INCLUDED IN
 THE BUILDING AREA IF SUCH AREAS ARE INCLUDED WITHIN THE
 HORIZONTAL PROJECTION OF THE ROOF OR FLOOR ABOVE.
  
 1D)(2) SHEET 021_S600 SECTION 4 INDICATES THE USE OF
 PLYWOOD SHEATHING, THIS MAYBE AN ISSUE IF THE BUILDING
 TYPE IS DECLARED EITHER A TYPE I OR II CONSTRUCTION.
 SEE 2017 FBC-B 603.1.1(1.2) FIRE RETARDANT TREATED WOOD
 MAYBE USED IN NONBEARING EXTERIOR WALLS WHERE FIRE
 RESISTANCE RATED CONSTRUCTION IS NOT REQUIRED.
  
 2) BOTH THE SITE DEMO PLAN D100S AND THE ARCHITECTURAL
 SITE PLAN A100S NEITHER OF THESE PLANS INDICATE WHERE
 THE WORK IS TO BE COMPLETED UNDER THIS PERMIT. IT?S
 ASSUMED UNDER THE SERVICE ADVISORS AREA BUT TO THE
 RIGHT OF THE BUILDING THERE APPEARS TO BE A SMALL
 BUILDING AT THE GATE ENTRY? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3) SHEET 016_S001 UNDER THE HEADING OF FOUNDATION NOTES
 THE LINE IS BLANK AS TO WHAT THE MINIMUM BEARING VALUE
 OF THE SOIL IS TO BE. THIS SHOULD BE A KNOWN FACTOR AS
 TO WHAT THE SOILS CAPACITY (ALLOWABLE) PER SQUARE FOOT
 FOR FILL AND FOR FOOTINGS? THE NOTE FURTHER INDICATES
 THE SOIL BEARING CAPACITY SHALL ALSO BE VERIFIED BY A
 SOILS ENGINEER.
 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 4) SHEETS S001, S002, S201, S600 & S680 ALL SHOW EITHER
 WELDED OR BOLTED CONNECTIONS TO OTHER STEEL FRAMING
 MEMBERS, THESE INSPECTIONS WILL NEED TO BE COMPLETED BY
 A 3RD PARTY ENGINEER. FOR FURTHER INFORMATION ON THIS
 INSPECTION CONTACT CHIEF BUILDING INSPECTOR KEN CONRAD
 8:00-9:00 (AM) AT 561-805-6666. ALL OTHER BUILDING
 INSPECTIONS WILL BE COMPLETED BY CITY INSPECTORS.
 2017 FBC-B WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR
 IS REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING
  
 5) SHEET S600 INDICATES PLYWOOD SUB-SHEATHING, DOES NOT
 INDICATE THICKNESS NOR GRADE, THIS SECTION IS TAKEN
 ABOVE THE WINDOW LINE BUT A901 THE PERSPECTIVE VIEW
 DOES SHOW PLYWOOD SHEATHING BELOW THE WINDOWS, PLEASE
 SHOW HOW COMPLIANCE WILL BE ACHIEVED WITH:
  
 2017 FBC-B 2304.12.1.5 WOOD SIDING. CLEARANCE BETWEEN
 WOOD SIDING AND EARTH ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM) OR LESS THAN 2
 INCHES (51 MM) VERTICAL FROM CONCRETE STEPS, PORCH
 SLABS, PATIO SLABS AND SIMILAR HORIZONTAL SURFACES
 EXPOSED TO THE WEATHER EXCEPT WHERE SIDING, SHEATHING
 AND WALL FRAMING ARE OF NATURALLY DURABLE OR
 PRESERVATIVE-TREATED WOOD.
  
 6) THE PRODUCT APPROVALS DOES NOT SHOW THE DESIGNERS
 REVIEW AND APPROVAL. 2017 W. P. B. 107.3.4. PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY
 FLORIDA ADMINISTRATIVE CODE RULE 61G20 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) THE KAWNEER TECHNICAL DRAWINGS ARE NOT A PRODUCT
 APPROVAL THAT SHOWS 3RD PARTY TESTING. 2017 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)( (B) WINDOWS & MULLIONS
  
 8) THE PRESSURES FOUND ON SHEET 016_S001 VULT AND VASD
 ARE LOW. THE WALL ZONE 4 THE NEGATIVE PRESSURES AVERAGE
 4.166 PSF LOW AND FOR WALL ZONE 5 THEY AVERAGE 5.166
 PSF LOW. 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
 WE WERE USING THE MEAN ROOF HEIGHT OF 15 FT. OUR TABLES
 FOR ZONE 4 & 5 ARE ONLY 0.01 PSF DIFFERENT THAN
 ENGINEERING EXPRESS TABLES FOR BUILDINGS < THAN 60
 FEET.
  
 9) IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved