| 2019-01-30 13:44:54 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 19010075 |
| | REVIEWED: JANUARY 30, 2019 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC[RE] = FBC EXISTING RESIDENTIAL |
| | FBC[E] = FBC ENERGY CONSERVATION |
| | FBC[R] = FBC RESIDENTIAL |
| | |
| | PROJECT DATA: |
| | 1. 501 FBC[RE] STATE THE LEVEL OF ALTERATION FOR WORK |
| | BEING PERFORMED. |
| | PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA. THIS |
| | WOULD BE A LEVEL 2 ALTERATION. |
| | OCCUPANCY = (R-3 FOR SINGLE FAMILY) |
| | TYPE OF WALL CONSTRUCTION = _________(VB?) |
| | RISK CATEGORY = ___(II) |
| | EXPOSURE CATEGORY = ___(B,C OR D) |
| | BUILDING CLASSIFICATION = __________(ENCLOSED) |
| | MEAN BLDG. HGT. = ___FT. ___IN.(THIS WILL BE THE HEIGHT |
| | MEASURED FROM THE GROUND TO IN BETWEEN EAVE AND ROOF |
| | PEAK) |
| | WIND SPEED V ULT = _____(170) |
| | WIND SPEED V ASD = _____(132) |
| | COMPONANT & CLADDING: |
| | FBC TABLE 301.2(2) FBC[R] |
| | DESIGN PRESSURE = +___ & -___ |
| | |
| | 2. 301.2(3) FBC[R] PROVIDE PRESSURE ON EACH WINDOW/DOOR |
| | AND INDICATE IF THE OPENING IS IN THE INTERIOR OR |
| | EXTERIOR ZONE. |
| | |
| | 3. 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS: |
| | GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN |
| | EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF |
| | SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED |
| | PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY |
| | SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE. |
| | |
| | 4. 503.1.1 FBC[E] BUILDING ENVELOPE ASSEMBLIES THAT ARE |
| | PART OF THE ALTERATION SHALL COMPLY WITH SECTION |
| | R402.1.2 OR R402.1.4, SECTIONS R402.2.1 THROUGH |
| | R402.2.13, R402.3.1, R402.3.2, R402.4.3 AND R402.4.5 |
| | HOW ARE ENERGY CODES BEING APPLIED? |
| | PROVIDE INSULATION VALUE OF CEILING ABOVE AND |
| | INSULATION AT IN-FILL LOCATIONS. |
| | |
| | 5. 103.1.1.2 FBC[RE] THE BUILDINGS OWNER, THE OWNERS |
| | ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNATED |
| | BY THE OWNER SHALL CERTIFY THAT THE BUILDING IS IN |
| | COMPLIANCE WITH THE CODE, AS PER SECTION 553.907, |
| | FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO |
| | BEGIN CONSTRUCTION OR RENOVATION. 553.907, FLORIDA |
| | STATUTES. |
| | |
| | 6. 301.2.1 FBC[R] PROVIDE DESIGN PRESSURES NEEDED FOR |
| | WINDOWS AND FOLDING GLASS DOOR SYSTEM FOR CLADDING AND |
| | COMPONENTS. |
| | |
| | 7. 107.3.1 FBC[AMENDED] PROVIDE PRODUCT APPROVAL FOR |
| | WINDOW MULL IF THE WINDOW OPENINGS CONSIST OF MORE THAN |
| | ONE WINDOW FRAME PER OPENING. |
| | 301.2(2) TABLE FBC[R] |
| | |
| | 8.PLEASE PROVIDE ONE ADDITIONAL COPY OF THE THREE |
| | PRODUCT APPROVALS 17-0420.04, 18-0627.01 AND 17-0420.12 |
| | THAT WERE PROVIDED. ONLY ONE SET WAS IN THE PERMIT SET, |
| | BUT WE NEED TWO SETS TOTAL. |
| | |
| | 9. IS THERE A STEPDOWN FROM THE INTERIOR SPACE? |
| | 10. HOW WILL THIS BE FILLED IN? |
| | 11. CAN THE REQUIRMENTS FOR THE NEXT TO CODE SECTIONS |
| | BELOW BE MET? |
| | |
| | 506.2.3 FBC[R] VAPOR RETARDER. A 6-MIL (0.006 INCH; 152 |
| | ?M) POLYETHYLENE OR APPROVED VAPOR RETARDER WITH JOINTS |
| | LAPPED NOT LESS THAN 6 INCHES SHALL BE PLACED BETWEEN |
| | THE CONCRETE FLOOR SLAB AND THE BASE COURSE OR THE |
| | PREPARED SUBGRADE WHERE NO BASE COURSE EXISTS. |
| | |
| | 318.1 FBC[R] TERMITE PROTECTION. TERMITE PROTECTION |
| | SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING |
| | SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND |
| | PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS |
| | OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE |
| | TREATMENT TO NEW CONSTRUCTION. SEE SECTION 202, |
| | ?REGISTERED TERMITICIDE.? UPON COMPLETION OF THE |
| | APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A |
| | CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE |
| | BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL |
| | COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE |
| | BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE |
| | PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN |
| | ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE |
| | FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER |
| | SERVICES.? |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |
| | |
| | |
| | |
| | |
| | |