| | 1ST REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. RE: PLAN SHEET A-2; PLUMBING FIXTURES IN THE |
| | KITCHEN, MASTER BATH, BATH #3, KITCHEN AND LAUNDRY ROOM |
| | HAVE BEE SUBSTANTIALLY RELACATED OR RECONFIGURED FROM |
| | THE EXISTING FLOOR PLAN SHOWN ON A-1 DEMO PLAN. PROVIDE |
| | A CODE COMPLIANT SANITARY RISER DIAGRAM PER WPB FBC |
| | 107.3.5.3 (12) TO REFLECT THE MODIFIED SYSTEM BEARING |
| | THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| | THE DESIGN PER WPB FBC 107.2.1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | |