| 2019-01-15 13:52:38 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #19010015 |
| | 1/15/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) MANUFACTURER'S SPECIFCATIONS FOR THE BREWHOUSE WERE |
| | NOT SUBMITTED. PLEASE SUBMIT THE SPECS WITH DIAGRAMS |
| | AND PRODUCT DATA INDICATING THE DESIGN AND OPERATING |
| | PRESSURE AND TEMPERATURE OF THE BREWHOUSE, AND LISTING |
| | AND LABELING. |
| | |
| | 2) PLEASE SUBMIT SPECS FOR THE BREWHOUSE VENT PIPE AND |
| | ROOF CAP, AND PROVIDE A DIAGRAM THAT SHOWS THE TOTAL |
| | RUN LENGTH OF THE VENT FROM THE TANK TO TERMINATION |
| | ABOVE THE ROOF- SEE TABLE 504.2(1) FBC FG. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |