Plan Review Notes
Plan Review Notes For Permit 19010002
Permit Number 19010002
Review Stop M
Sequence Number 2
Notes
Date Text
2019-03-11 17:22:322ND REVIEW FBC-2017 MECHANICAL
 PERMIT #19010002
 3/11/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AN ELECTRICAL PLAN SHEET HAS BEEN UPLOADED UNDER THE
 TITLE OF M102 WHICH IS SUPPOSED TO BE A MECHANICAL PLAN
 SHEET- SECTION 107 WPB.
  
 2) THE NEW M101 PLAN SHEET WAS NOT UPLOADED CORRECTLY
 AND ONLY APPEARS IN THE PRINTABLE FORMAT- SECTION 107
 WPB.
  
 3) THIS IS AN ELECTRONIC SUBMITTAL. PLEASE DO NOT
 UPLOAD DOCUMENTS THAT HAVE BEEN FOLDED OVER AND STAMPED
 WITH SHOP DRAWING APPROVALS. THE TEXT AND DETAILS ARE
 HIDDEN BEHIND THE STAMPS- SECTION 107 WPB.
  
 4) THE SUBMITTAL FOR THE ROOF STAND IS AN OUTDATED COPY
 FROM 2014. PLEASE PROVIDE UPDATED ENGINEERING IN
 COMPLIANCE WITH THE FBC-7 SIXTH EDITION.
  
 5) THE CHANGE IN VALUE TO $26,000 IS ACCEPTED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  