Plan Review Notes
Plan Review Notes For Permit 19010002
Permit Number 19010002
Review Stop M
Sequence Number 1
Notes
Date Text
2019-01-16 16:38:241ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19010002
 1/16/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHOW THE LOCATIONS OF THE REMOTE CONDENSER AND
 REFRIGERANT PIPING RUNS FROM THE COOLER TO THE
 CONDENSER- SECTION 107.2.1 WPB, AND SECTION 1107 FBC M.
  
 2) PROVIDE ENGINEERING FOR INSTALLATION OF THE
 CONDENSER- SECTION 301.15 FBC M.
  
 3) THE $4,000 JOB VALUE ON THE APPLICATION IS LOW FOR A
 13'X10' WALK IN COOLER AND REFRIGERATION SYSTEM .
 PLEASE PROVIDE AN ACCURATE VALUE THAT INCLUDES LABOR,
 MATERIALS AND THE COST OF THE COOLER AND REFRIGERATION
 SYSTEM- SECTION 109.3 WPB
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  