| 2019-01-29 10:47:03 | MECHANICAL PLAN REVIEW | | | | | | APPROVAL IS PENDING: | | | | | | 1. FBC R M1401.3 PROVIDE ENERGY CALCULATIONS. | | | 2. CITY OF WPB LOCAL AMENDMENTS 107 PROVIDE EQUIPMENT | | | SCHEDULE ON MECHANICAL PAGE OF PLANS. | | | 3. CITY OF WPB LOCAL AMENDMENTS 107 PROVIDE | | | CLARIFICATION OF DUCT SIZE. PLANS INDICATE 7" AND 6" ON | | | THE SAME SECTION OF DUCTWORK FOR THE KITCHEN DROP. | | | 4. FBC R M1307.2 PROVIDE ENGINEERING FOR EXTERIOR | | | CONDENSING UNIT TIE-DOWN ATTACHMENTS. |
|