| 2019-04-15 17:17:14 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18120892 |
| | 4/15/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A2.0 & M1.1: MISSING FIRE DAMPERS FOR THE 8/8 |
| | TRANSFER DUCT AND THE 22/14 O/A DUCT PENETRATING THE |
| | FIRE-RATED CHEM STORAGE ROOM WALLS- SECTION 607.5.2 FBC |
| | M. |
| | |
| | 2) A2.0 & M1.1: THE 6/6 EXHAUST DUCT FROM THE CHEM |
| | STORAGE ROOM MUST BE ENCLOSED IN FIRE-RESISTANT |
| | CONSTRUCTION FROM THE POINT OF THE FIRE-RATED WALL |
| | PENETRATION TO THE OUTLET TERMINAL- SECTION 510.7.3 FBC |
| | M. |
| | |
| | 3) A100, A603, & M1.1: AS PREVIOUSLY NOTED, IT APPEARS |
| | THAT AIR IS BEING RECIRCULATED VIA TRANSFER GRILLS FROM |
| | THE SOLID ROOM INTO THE HALLWAY WHICH IS PROHIBITED- |
| | SEE TABLE 403.3.1.1 FOOTNOTE G- RECIRCULATION OF AIR |
| | FROM THE LAB ROOMS IS PROHIBITED WITH THE EXCEPTION OF |
| | 10% OF THE AIRSTREAM FROM THE SPACES IS PERMITTED TO BE |
| | RECIRCULATED. THE ROOM IS NOT LABELED "LAB" HOWEVER |
| | THERE IS A FUME HOOD IN THE ROOM AND OTHER PROCESSING |
| | EQUIPMENT AND OVENS. |
| | |
| | 4) A100, A603, & M1.1: SHOW THE EXHAUST DUCT RUN AND |
| | TERMINATION LOCATION FOR THE EXHAUST HOOD IN THE |
| | MICROBIOLOGY ROOM- SECTION 510.6.7 FBC M. |
| | |
| | 5) A100, A603, & M1.1: PLEASE PROVIDE A NARRATIVE THAT |
| | DESCRIBES THE PROCESSES THAT OCCUR UNDER THE HOODS IN |
| | THE LAB, SOLIDS, AND MICROBIOLOGY ROOMS. A) PROVIDE A |
| | SEQUENCE OF OPERATION THAT INCLUDES HOW MAKE UP AIR |
| | WILL BE AUTOMATICALLY PROVIDED- SECTION 510.6.5 FBC M |
| | B) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE HOODS, FANS, AND |
| | EXHAUST DUCTWORK- SECTIONS 304.1 & 510.6.3 FBC M. |
| | |
| | 6) M1.100: VERIFY ALL EXHAUST OUTLET CLEARANCES ARE IN |
| | COMPLIANCE WITH SECTION 501.3.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |