| 2019-04-19 15:01:50 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 18120892 |
| | ADD: 4375 EASLEY DR. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 561-835-7406 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JAN. 28/2019 |
| | ACTION: DENIED |
| | |
| | 1) OK. |
| | |
| | 2) OK. |
| | |
| | ORIGINAL COMMENT: |
| | 3) THE SHEET 023-S-2 UNDER THE HEADING OF FOUNDATIONS |
| | NOTE # 1 INDICATES THERE IS A SOILS REPORT PREPARED BY |
| | FEDERAL ENGINEERING AND TESTING, DATED AUGUST 24, 2018. |
| | PLEASE SUBMIT A PAPER ORIGINAL SIGNATURE AND SEALED OR |
| | SUBMIT ELECTRONICALLY WITH AN ELECTRONIC SIGNATURE. |
| | |
| | RESPONSE: |
| | SOIL TEST REPORT SUBMITTED DOESN'T HAVE A DIGITAL |
| | SIGNATURE. UPLOAD REPORT WITH ENGINEER'S DIGITAL |
| | SIGNATURE OR SUBMIT HARD COPIES WITH ORIGINAL SEAL AND |
| | SIGNATURE AS REQUIRED BY CHAPTER 471 WHEN SUBMITTING |
| | DOCUMENTS FOR PUBLIC RECORDS. |
| | |
| | 4A) OK. |
| | |
| | 4B) OK. |
| | |
| | 5) PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR: |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. CONTRACTOR TO ADVICE IF SUBMITTING PRODUCT |
| | APPROVALS AS DEFERRED SUBMITTAL. PROVIDE COMPLETE |
| | INFORMATION PRIOR TO INSTALLATION TO AVOID |
| | CONFLICTS/DELAYS. ALL PRODUCT APPROVALS NEED TO BE |
| | APPROVED IN WRITING BY DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL) |
| | |
| | (A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| | CONCRETE AND OR INSULATION, |
| | |
| | 6) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| | PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| | RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| | DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| | IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| | MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| | INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| | PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 |
| | INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| | FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| | INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| | LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 7) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| | ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| | FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| | LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| | ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| | BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| | COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| | CALCULATION PREPARED, SIGNED AND |
| | SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| | REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. |
| | 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| | VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS |
| | AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE |
| | INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| | INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| | THE SPECIFIC SITE. |
| | |
| | 8) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 9) OK. NOTED ON DRAWINGS. |
| | THE ARCHITECTURAL AND STRUCTURAL SHEETS INDICATE THE |
| | ADDITION IS TO HAVE A BAR JOIST AND METAL DECK ROOF |
| | SYSTEM. PLEASE HAVE A 3RD PARTY ENGINEER REVIEW ALL |
| | WELDED JOINTS AND BOLTED JOINTS AND SUPPLY A SIGNED AND |
| | SEALED LETTER OF THE INSPECTIONS AT THE TIME OF THE |
| | WINDOW BUCK INSPECTION AND BEFORE THE INTERIOR FRAMING |
| | INSPECTION. IF THERE IS ANY QUESTIONS IN REGARDS TO |
| | BUILDING INSPECTIONS PLEASE CONTACT THE CHIEF BUILDING |
| | INSPECTOR KEN CONRAD AT 561-805-6666. |
| | WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS |
| | REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS & |
| | WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN |
| | ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF |
| | INSPECTION. |
| | 2017 FBC-B 2204.1 WELDING |
| | 2017 FBC-B 2204.2 BOLTING. |
| | |
| | 10) NEW COMMENTS ON ENERGY CALCULATIONS: |
| | A) NEED ARCHITECT'S NAME AND LICENSE NUMBER ON THE |
| | ENERGY CALCULATIONS. SEE FOOTNOTE ON CERTIFICATIONS |
| | PAGE. ALSO. SEE SEC. C103.1.1.1.2 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | B) NEED THE OWNER'S OR OWNER'S AUTHORIZED AGENT TO |
| | CERTIFY THE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | C103.1.1.2 FBC-ENERGY CONSERVATION |
| | |
| | |
| | 11) OK. |
| | |
| | |
| | 12) OK. |
| | |
| | 13) OK. |
| | |
| | 14) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |