| Date |
Text |
| 2019-01-22 17:47:29 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18120892 |
| | 1/22/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS M1.1 & M2.1: EXHAUST VENTILATION AT A RATE OF |
| | 1.0 CFMS PER SF. IS REQUIRED FOR THE LAB ROOMS- TABLE |
| | 403.3.1.1 FBC M. PLEASE PROVIDE THE CALCULATIONS AND |
| | THE REQUIRED EXHAUST SYSTEMS. THE ROOMS REQUIRING |
| | EXHAUST VENTILATION ARE THE EXISTING LAB, THE SOLID |
| | ROOM, AND THE MICROBIOLOGY ROOM. THE CURRENT PLAN SHOWS |
| | EXHAUST DUCTS IN THE LAB AND THE SOLID ROOM BUT NO |
| | CALCULATIONS OR FAN INFORMATION TO VERIFY COMPLIANCE. |
| | PLEASE NOTE THAT CHEMICAL FUME HOODS REQUIRE LOCAL |
| | EXHAUST, BUT THE 1.0 CFM RATE IS REQUIRED FOR THE |
| | ENTIRE ROOM. IF CHEMICAL FUME HOODS ARE TO BE INSTALLED |
| | PLEASE PROVIDE EQUIPMENT SCHEDULES AND SHOW THE |
| | LOCATIONS OF THE HOODS. |
| | |
| | 2) M1.1: REFER TO TABLE 403.3.1.1 FOOTNOTE G- |
| | RECIRCULATION OF AIR FROM THE LAB ROOMS IS PROHIBITED |
| | WITH THE EXCEPTION OF 10% OF THE AIRSTREAM FROM THE |
| | SPACES IS PERMITTED TO BE RECIRCULATED. THE CURRENT |
| | PLAN SHOWS RECIRCULATED AIR FROM THE LABS INTO THE |
| | ADJACENT OFFICES AND HALLWAY. |
| | |
| | 3) M1.1: CLARIFY HOW O/A IS BEING PROVIDED TO THE |
| | SPACES. THERE ARE TWO 22X14" DUCTS RETURNING AIR TO THE |
| | AIR HANDLERS VIA TWO 42X24" RETURN GRILLES THAT ARE |
| | SHOWN OUTSIDE THE PERIMETER OF THE SPACES. ARE THESE |
| | GRILLES MISLABELED? |
| | |
| | 4) REFER TO SECTION 510.2 FBC M AND VERIFY COMPLIANCE: |
| | 510.2 WHERE REQUIRED. |
| | |
| | A HAZARDOUS EXHAUST SYSTEM SHALL BE REQUIRED WHEREVER |
| | OPERATIONS INVOLVING THE HANDLING OR PROCESSING OF |
| | HAZARDOUS MATERIALS, IN THE ABSENCE OF SUCH EXHAUST |
| | SYSTEMS AND UNDER NORMAL OPERATING CONDITIONS, HAVE THE |
| | POTENTIAL TO CREATE ONE OF THE FOLLOWING CONDITIONS: |
| | |
| | 1.A FLAMMABLE VAPOR, GAS, FUME, MIST OR DUST IS PRESENT |
| | IN CONCENTRATIONS EXCEEDING 25 PERCENT OF THE LOWER |
| | FLAMMABILITY LIMIT OF THE SUBSTANCE FOR THE EXPECTED |
| | ROOM TEMPERATURE. |
| | |
| | 2.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD |
| | RATING OF 4 IS PRESENT IN ANY CONCENTRATION. |
| | |
| | 3.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD |
| | RATING OF 1, 2 OR 3 IS PRESENT IN CONCENTRATIONS |
| | EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL CONCENTRATION |
| | OF THE SUBSTANCE FOR ACUTE INHALATION TOXICITY. |
| | |
| | EXCEPTION: LABORATORIES, AS DEFINED IN SECTION 510.1, |
| | EXCEPT WHERE THE CONCENTRATIONS LISTED IN ITEM 1 ARE |
| | EXCEEDED OR A VAPOR, GAS, FUME, MIST OR DUST WITH A |
| | HEALTH-HAZARD RATING OF 1, 2, 3 OR 4 IS PRESENT IN |
| | CONCENTRATIONS EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL |
| | CONCENTRATION OF THE SUBSTANCE FOR ACUTE INHALATION |
| | TOXICITY. |
| | |
| | 5) REFER TO SECTION 414.1.3 FBC B.AND PROVIDE THE |
| | MAXIMUM QUANTITIES OF HAZARDOUS MATERIALS TO BE STORED, |
| | AND USED IN OPEN OR CLOSED SYSTEMS ETC. PLEASE SUBMIT |
| | MSDS SHEETS FOR EACH MATERIAL. |
| | |
| | 6) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF |
| | THE AC CONDENSERS- SECTION 301.15. |
| | |
| | 7) PROVIDE A LAB EQUIPMENT LAYOUT PLAN AND EQUIPMENT |
| | SCHEDULE- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |