| 2019-01-02 12:00:30 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18120878 |
| | 1/2/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE $3000.00 VALUE LISTED ON THE APPLICATION IS LOW |
| | FOR THE INSTALLATION OF A NEW 5-TON AC SYSTEM AND |
| | DUCTWORK. PERMIT VALUE IS BASED ON LABOR, MATERIALS, |
| | EQUIPMENT, SITE WORK, DESIGN FEES, AND OVER HEAD AND |
| | PROFIT PER SECTION 109.3 WPB. PLEASE PROVIDE A CONTRACT |
| | AND INVOICES TO VERIFY ACCURATE JOB VALUE. |
| | |
| | 2) A DUCT SMOKE DETECTOR IS REQUIRED IN THE SUPPLY AIR |
| | SYSTEM OF THE NEW 5-TON AC SYSTEM PER SECTION 606.2.1 |
| | FBC M.. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF |
| | THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE |
| | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| | |
| | 3) THE 500 CFMS OF AIR IN OFFICE 3 DOES NOT APPEAR TO |
| | BE CONSISTENT WITH THE AC CALULATIONS WHICH SHOWS THE |
| | COOLING LOADS TO BE THE SAME AS OFFICE 2. OFFICE 2 HAS |
| | ONLY 150 CFMS OF AIR PROVIDED. |
| | |
| | 4) ENGINEERED WIND LOAD CALCULATIONS ARE REQUIRED FOR |
| | INSTALLATION OF THE ROOFTOP CONDENSER AND STAND- |
| | SECTION 301.15 FBC M. IN ADDITION PLEASE SUBMIT A FL. |
| | PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE CONDENSER |
| | STAND. |
| | |
| | 5) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307.2 |
| | FBC M. |
| | |
| | 6) PROVIDE AN ELECTRICAL PLAN AND AN ELECTRIC |
| | SUB-PERMIT- SECTION 107 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |