| 2019-01-17 12:08:59 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. RE: PLAN SHEET P-1; SANITARY RISER. CORRECT ON PLAN |
| | AS NOTED BELOW PER WPB FBC 107.2.1. |
| | A.2" HUB DRAIN SERVICING THE WATER HEATER |
| | 1) A P-TRAP REQUIRED PER FBC PL 1002.1. |
| | 2) A SEPERATE VENT IS REQUIRED FOR THE TRAPPED FIXTURE |
| | DRAIN PER FBC PL 901.2.1 AND SECTION 909. LENGTH OF |
| | FIXTURE DRAIN SHALL COMPLY WITH FBC PL TABLE 909.1. |
| | PLEASE NOTE THAT THE PROVISIONS OF FBC PL 911 AND 912 |
| | DO NOT APPLY TO THIS INSTALLATION. |
| | B. LAUNDRY |
| | 1) FIXTURE BRANCH SERVICING THE TWO (2) CLOTHES WASHER |
| | FIXTURE DRAINS SHALL BE MINIMUM 3" SIZE PER FBC PL |
| | 406.2. |
| | 2) CLOTHES WASHER FIXTURE DRAINS AND TRAPSD SHALL BE |
| | MINIMUM 2" SIZE PER FBC PL 406.2 AND TABLE 709.1. |
| | 3) UPSTREAM CLOTHES WASHER FIXTURE DRAIN IS S-TRAPPED |
| | WHICH IS PROHIBITED PER FBC PL 1002.3 (5). SHOW |
| | COMPLIANCE WITH FBC PL SECTION 909. |
| | C. SHAMPOO BACKWASH SINKS |
| | 1) IDENTIFY EACH TRAP ON ISOMETRIC AS THE NOTED |
| | INTERCEPTOR, ZURN Z1175 PER WPB FBC 107.2.1. |
| | |
| | 2. RE: PLAN SHEET P-1; WATER RISER ISOMETRIC. CORRECT |
| | ON PLAN AS NOTED BELOW PER WPB FBC 107.2.1. |
| | A. EXISTING WATER COLD WATER SERVICE/DISTRIBUTION |
| | APPEARS TO BE COMMON TO THE ENTIRE BUILDING. PROVIDE |
| | SIZING OF EXISTING COMMON SERVICE/DISTRIBUTION AND |
| | CALCULATIONS WHICH INCLUDE THE EXISTING USAGE IN THE |
| | BUILDING PER WPB FBC 107.2.1. |
| | B. SHOW THE FULL EXTENT OF THE HOT WATER RETURN LINE ON |
| | THE RISER DIAGRAM SHOWING COMPLIANCE WITH FBC PL 607.2 |
| | PER WPB FBC 107.2.1. |
| | C. PROVIDE SHUT OFF VALVE FOR SERVICE INTO THE UNIT PER |
| | FBC 606.1. |
| | |
| | 3. WATER HEATER |
| | A. PROVIDE A SCHEMATIC OF THE SPECIFIED BOTTOM FED |
| | WATER HEATER WITH RECIRC PUMP, EXPANSION TANK AND |
| | PIPING SHOWING ALL SIZING, VALVING (INCLUDING CHECK |
| | VALVES AND VACUUM RELIEF VALVE) AND PIPING |
| | INTERCONNECTIONS PER WPB FBC 107.2.1. |
| | B. PROVIDE SIZE OF EXPANSION TANK SHOWING COMPLIANCE |
| | WITH FBC PL 607.3 PER WPB FBC 107.2.1. |
| | |
| | 4. PROVIDE A FIXTURE SCHEDULE WITH THE FOLLOWING |
| | INFORMATION PER WPB FBC 107.2.1. |
| | A. MANUFACTURER NAME AND MODEL # WITH NOTE "EQUAL TO". |
| | INCLUDE FAUCET FOR LAVATORY AND MOP SINK.INDICATE TYPE |
| | OF BACKFLOW PREVENTION TO PROVIDE FOR MOP SINK FAUCET. |
| | 1) IF BY OWNER, THEN NOTE IN SCHEDULE. INDICATE THE |
| | TYPE OF BACKFLOW PREVENTION TO PROVIDE WHERE APPLICABLE |
| | IN ACCORDANCE WITH THE REQUIREMENTS OF FBC PL SECTION |
| | 608. PLEASE NOTE THAT SUBMITTAL DATA FOR OWNER SUPPLIED |
| | EQUIPMENT COVERED UNDER THE PLUMBING SCOPE WILL HAVE TO |
| | BE SUBMITTED TO THE BUILDING DEPARTMENT AND APPROVED |
| | AND IN PLACE ON THE JOBSITE PRIOR TO FINAL INSPECTION. |
| | B. WATER USAGE OF FIXTURE |
| | C. ADA COMPLIANCE FOR THE WATER CLOSET, LAVATORY AND |
| | ELECTRIC WATER COOLER IN ACCORDANCE WITH FBC ACC |
| | CHAPTERS 2, 3 AND 6. |
| | |
| | 5. PER WPB FBC 107.2.1, PROVIDE SCHEDULE AND SPEC FOR |
| | WATER HEATER AND RECIRC PUMP; INCLUDE ELECTRICAL |
| | CHARACTERISTICS OF THE EQUIPMENT. |
| | |
| | 6. IS EXISTING TOILET ROOM ADA COMPLIANT? IF SO, THEN |
| | STATE ON THE PLANS AND SHOW TURNING RADIUS FOR |
| | WHEELCHAIR PER WPB FBC 107.2.1. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |