| 2019-01-10 17:44:00 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18120854 |
| | 1/10/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) BEAUTY SALONS SHALL HAVE EXHAUST VENTILATION SYSTEMS |
| | SIZED AT A RATE OF 0.6 CFMS PER SF. PER TABLE 403.3.1.1 |
| | FBC M. PLEASE REVISE THE PLANS TO MEET COMPLIANCE. |
| | |
| | 2) SHEET M-2: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| | SUPPLY SYSTEMS OF THE NEW 5-TON RTU'S PER SECTION |
| | 606.2.1 FBC M. PLEASE PROVIDE SYMBOLS ON THE PLAN TO |
| | SHOW THE LOCATIONS. |
| | |
| | 3) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF |
| | THE RTU'S AND CURBS- SECTION 301.15 FBC M. |
| | |
| | 4) M-2: DRYER EXHAUST DUCTS SHALL BE EQUIPPED WITH |
| | BACKDRAFT DAMPERS, NOT MOTORIZED DAMPERS AS INDICATED |
| | IN NOTE #3- SECTION 504.4 FBC M. |
| | |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYERS- |
| | SECTION 504.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |