2019-05-21 15:21:02NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 ORIGINAL COMMENT:
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 NOTE: DRAINAGE PLAN SHOWN ON SHEET SP-1 IS INCOMPLETE.
 IT DOESN'T SHOW THE PROPOSED DRAINAGE FOR ENTIRE LOT
 AND THE ELEVATIONS SHOWN ON SECTION/DETAILS A-A AND B-B
 ON SAME SHEET DON'T MATCH ELEVATIONS SHOWN ON THE
 REVISED SURVEY SUBMITTED. REVISE AS REQUIRED AND
 PROVIDE COMPLETE DRAINAGE PLAN.
  
 RESPONSE:
 ENGINEER OF RECORD WAS CHANGED. NO DRAINAGE PLAN
 SUBMITTED AT THIS TIME.
  
 ORIGINAL COMMENT.
 2- COMPONENT & CLADDING DESIGN PRESSURES SHOWN ON SHEET
 CVR AND DESIGN PRESSURES SHOWN ON SHEET A2 DON'T MATCH.
 IN ADDITION, IT LOOKS LIKE THE DESIGN PRESSURES ON
 SHEET CVR ARE GIVEN IN NOMINAL DESIGN WIND SPEEDS
 (ASD), WHILE THE DESIGN PRESSURES ON SHEET A2 ARE GIVEN
 IN ULTIMATE DESIGN WIND SPEEDS (VULT). REVISE AS
 REQUIRED TO MATCH AND PROVIDE ALL DESIGN PRESSURES IN
 NOMINAL WIND SPEEDS (ASD) AS REQUIRED BY SEC.
 R301.2.1.3 FBC-RESIDENTIAL. THIS WILL AVOID CONFLICTS
 ALSO.
  
 RESPONSE:
 A)ENGINEER OF RECORD WAS CHANGED.DESIGN PRESSURES SHOWN
 FOR THE HORIZONTAL ROLLING WINDOWS SEEMS TO BE TOO LOW
 BASED ON THE BUILDING EXPOSURE. PROVIDE CALCULATIONS
 SHOWING WHY THEY ARE SO LOW. SEC. 107.2.1.2 CITY
 AMENDMENTS. ALSO, CLARIFY WHY THE DESIGN PRESSURES FOR
 HORIZONTAL ROLLING WINDOW LOCATED IN BEDROOM #2 ARE THE
 SAME IF THIS WINDOW SEEMS TO BE LOCATED IN ZONE 5.
 (NOTE: ACCORDING TO FIGURE R301.2(7) THE MINIMUM
 DISTANCE FOR ZONE 5 IS 4'-0")
  
 B)NEW ENGINEER OF RECORD TO PROVIDE CALCULATIONS TO
 CLARIFY WHY THE DESIGN PRESSURES FOR THE HORIZONTAL
 ROLLING WINDOWS ARE DIFFERENT THAN DESIGN PRESSURES FOR
 THE SINGLE HUNG WINDOWS?. DESIGN PRESSURES ARE BASED ON
 EFFECTIVE WIND AREA NOT TYPE OF WINDOW. SEC. 107.2.1.2
 CITY AMENDMENTS.
  
 C) DESIGN PRESSURES FOR OVERHEAD GARAGE DOOR ARE NOT
 LEGIBLE. REVISE AS REQUIRED AND COORDINATE WITH ITEMS
 @(A) AND 2(B) ABOVE. SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 3- REVISE DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON
 THE EXTERIOR ELEVATIONS ON SHEET A1 AND A2 FOR LIVING
 ROOM WINDOW AND BEDROOM #2 WINDOW. THEY ARE LOCATED IN
 END ZONE "B" NOT INTERIOR ZONE "A". FIGURE R301.2(7)
 FBC-RESIDENTIAL REQUIRES 4-MIN FOR END ZONE. REVISE AS
 REQUIRED.
  
 RESPONSE:
 COORDINATE WITH RESPONSES TO ITEM #2 ABOVE.
  
 4- OK.
  
 5- OK.
  
 6- OK.
  
 7- OK.
  
 ORIGINAL COMMENT:
 8- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 BY SEC. R807 FBC-RESIDENTIAL.
  
 RESPONSE:
 SIZE OF ATTIC ACCESS WAS NOT SPECIFIED. SPECIFY SIZE.
  
 9-OK.
  
 10- OK.
  
 11- OK.
  
 12- OK.
  
 13- OK.
  
 14- OK.
  
 15- OK.
  
 16- OK.
  
 17- ENERGY CALCULATIONS SUBMITTED:
  
 ORIGINAL COMMENT:
 A)THE BUILDING'S OWNER, THE OWNER'S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE PRIOR TO RECEIVING THE PERMIT AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. OWNER OR LEGALLY
 AUTHORIZED AGENT TO CERTIFY AT THE BOTTOM OF FORM.
  
 ORIGINAL COMMENT:
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 RESPONSE:
 NOT DONE AND NOW IS MISSING MORE INFORMATION LIKE
 PERMIT OFFICE, JURISDICTION NUMBER. PROVIDE COMPLETE
 INFORMATION.
  
 C) OK.
  
 ORIGINAL COMMENT:
 D) REVISE ITEM #9(B). THE MATERIAL OF ADJACENT WALL
 FRAME IS NOT WOOD. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT DONE.
  
 E)OK.
  
 ORIGINAL COMMENT:
 F)WINDOWS FRAME MATERIAL SPECIFIED ON PAGE 3 OF 4
 DOESN'T MATCH PLANS AND PRODUCT APPROVALS SUBMITTED.
 REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT DONE.
  
 NEW COMMENTS:
 G)NUMBER OF BEDROOMS SHOWN ON PAGE 1 OF 4 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 H)DUCTS R-VALUE SPECIFIED ON PAGE 1 OF 4 DOESN'T MATCH
 PLANS. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 I)NUMBER OF OCCUPANTS SPECIFIED ON PAGE 2 OF 4 NEED TO
 BE REVISED. COORDINATE WITH REVISE NUMBER OF BEDROOMS
 SHOWN ON PLANS. COORDINATE WITH ITEM #17(G) ABOVE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 J)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 ORIGINAL COMMENT:
 18- PRODUCT APPROVALS WILL BE REVIEWED ONCE THE DESIGN
 PRESSURES ARE CLARIFIED. SEE COMMENT #2 ABOVE. NOTE:
 ENGINEER OF RECORD TO REVIEW AND APPROVE THEM PRIOR TO
 SUBMITTAL.
 NOTE: SHUTTERS NEED COMPLETE INSTALLATION SCHEDULE. SEE
 CITY SAMPLE.
  
 RESPONSE:
 DESIGN PRESSURES NEED TO BE REVISED AGAIN. SEE COMMENT
 #2.
 NOTE: IT LOOKS LIKE HORIZONTAL ROLLING WINDOWS FLORIDA
 PRODUCT APPROVAL FL14994-R4 SUBMITTED DON'T MEET THE
 REQUIRED DESIGN PRESSURES. SAME THING APPLIES FOR SOME
 SINGLE HUNG WINDOWS. SEE ALL WINDOW SIZES SPECIFIED ON
 PLANS AND DESIGN PRESSURES SHOWN ON THE PRODUCT
 APPROVAL PRIOR TO SUBMITTAL. ENGINEER TO REVIEW AND
 APPROVE PRIOR TO SUBMITTAL.
  
 19- OK.
  
 NEW COMMENTS:
 20- PROVIDE OVERHEAD GARAGE DOOR STRUCTURAL BUCK
 DETAIL. SEC. 301.2.1 FBC-RESIDENTIAL. PLANS DON'T SHOW
 ANY DETAIL.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  