2019-01-15 15:41:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET P-1; PLUMBING RISER
 A. PER FBC RES P3108.1, "EACH WET VENTED FIXTURE DRAIN
 SHALL CONNECT DIRECTLY TO THE HORIZONTAL WET VENT." IN
 THE CASE OF THE MASTER BATH, CONNECT THE SHOWER DRAIN
 TO THE HORIZONTAL WET VENT DOWN STREAM OF THE VERTICAL
 PORTION OF THE WET VENT. IN THE CASE OF BATH #2,
 CONNECT THE WATER CLOSET TO THE HORIZONTAL WET VENT
 DOWNSTREAM FROM THE VERTICAL PORTION OF THE WET VENT.
 B. THE HORIZONTAL BRANCH SERVICING THE CLOTHES WASHER
 SHALL BE 3" WHEN VENTED BY A STUDOR AIR ADMITTANCE
 VALVE IN ACCORDANCE WITH THE MANUFACTURER'S DESIGN
 CRITERIA AND INSTALLATION INSTRUCTIONS.
 2. RE: PLAN SHEET P-1; WATER HEATER DETAIL
 A. PROVIDE PAN WITH DRAIN IN ACCORDANCE WITH FBC RES
 P2801.6, P2801.6.1 AND P2801.6.2.
 B. PROVIDE THERMAL EXPANSION CONTROL DEVICE IN COLD
 WATER SUPPLY TO WATER HEATER PER FBC RES P2903.4
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  