| 2019-01-15 15:41:45 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. RE: PLAN SHEET P-1; PLUMBING RISER |
| | A. PER FBC RES P3108.1, "EACH WET VENTED FIXTURE DRAIN |
| | SHALL CONNECT DIRECTLY TO THE HORIZONTAL WET VENT." IN |
| | THE CASE OF THE MASTER BATH, CONNECT THE SHOWER DRAIN |
| | TO THE HORIZONTAL WET VENT DOWN STREAM OF THE VERTICAL |
| | PORTION OF THE WET VENT. IN THE CASE OF BATH #2, |
| | CONNECT THE WATER CLOSET TO THE HORIZONTAL WET VENT |
| | DOWNSTREAM FROM THE VERTICAL PORTION OF THE WET VENT. |
| | B. THE HORIZONTAL BRANCH SERVICING THE CLOTHES WASHER |
| | SHALL BE 3" WHEN VENTED BY A STUDOR AIR ADMITTANCE |
| | VALVE IN ACCORDANCE WITH THE MANUFACTURER'S DESIGN |
| | CRITERIA AND INSTALLATION INSTRUCTIONS. |
| | 2. RE: PLAN SHEET P-1; WATER HEATER DETAIL |
| | A. PROVIDE PAN WITH DRAIN IN ACCORDANCE WITH FBC RES |
| | P2801.6, P2801.6.1 AND P2801.6.2. |
| | B. PROVIDE THERMAL EXPANSION CONTROL DEVICE IN COLD |
| | WATER SUPPLY TO WATER HEATER PER FBC RES P2903.4 |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |
| | |