Plan Review Notes
Plan Review Notes For Permit 18120817
Permit Number 18120817
Review Stop B
Sequence Number 1
Notes
Date Text
2019-01-18 17:41:11NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 NOTE: DRAINAGE PLAN SHOWN ON SHEET SP-1 IS INCOMPLETE.
 IT DOESN'T SHOW THE PROPOSED DRAINAGE FOR ENTIRE LOT
 AND THE ELEVATIONS SHOWN ON SECTION/DETAILS A-A AND B-B
 ON SAME SHEET DON'T MATCH ELEVATIONS SHOWN ON THE
 REVISED SURVEY SUBMITTED. REVISE AS REQUIRED AND
 PROVIDE COMPLETE DRAINAGE PLAN.
  
 2- COMPONENT & CLADDING DESIGN PRESSURES SHOWN ON SHEET
 CVR AND DESIGN PRESSURES SHOWN ON SHEET A2 DON'T MATCH.
 IN ADDITION, IT LOOKS LIKE THE DESIGN PRESSURES ON
 SHEET CVR ARE GIVEN IN NOMINAL DESIGN WIND SPEEDS
 (ASD), WHILE THE DESIGN PRESSURES ON SHEET A2 ARE GIVEN
 IN ULTIMATE DESIGN WIND SPEEDS (VULT). REVISE AS
 REQUIRED TO MATCH AND PROVIDE ALL DESIGN PRESSURES IN
 NOMINAL WIND SPEEDS (ASD) AS REQUIRED BY SEC.
 R301.2.1.3 FBC-RESIDENTIAL. THIS WILL AVOID CONFLICTS
 ALSO.
  
 3- REVISE DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON
 THE EXTERIOR ELEVATIONS ON SHEET A1 AND A2 FOR LIVING
 ROOM WINDOW AND BEDROOM #2 WINDOW. THEY ARE LOCATED IN
 END ZONE "B" NOT INTERIOR ZONE "A". FIGURE R301.2(7)
 FBC-RESIDENTIAL REQUIRES 4-MIN FOR END ZONE. REVISE AS
 REQUIRED.
  
 4- MASTER BEDROOM EMERGENCY ESCAPE AND RESCUE OPENING
 IS NOT CLEAR. INFORMATION SHOWN ON DOOR SCHEDULE, FLOOR
 PLAN AND PROPOSED SOUTH ELEVATION DON'T MATCH. REVISE
 AS REQUIRED TO COMPLY WITH SEC. R310.2 FBC-RESIDENTIAL.
  
 5- IT LOOKS LIKE WINDOWS FOR BEDROOM #2, #3 AND #4
 DON'T COMPLY WITH THE EMERGENCY ESCAPE AND RESCUE
 OPENING AS REQUIRED BY SEC. R310.2.1 FBC-RESIDENTIAL.
 IT LOOKS LIKE A 47.5" X 47.5" HORIZONTAL SLIDING WINDOW
 DOESN'T PROVIDE THE 20" MIN. CLEAR WIDTH OPENING.
 PROVIDE WINDOW MANUFACTURER'S CUT SHEETS SHOWING THAT
 PROPOSED WINDOW SIZE WILL MEET ALL THE EGRESS
 REQUIREMENTS.
  
 6- PROVIDE CARBON MONOXIDE ALARMS IN THE LOCATIONS
 REQUIRED BY SEC. R315.1 FBC-RESIDENTIAL.
  
 7- PROVIDE DOOR THAT PROVIDES A 29" CLEAR DOOR OPENING
 IN THE BATHROOM WITH MAXIMUM POSSIBLY PRIVACY.
 AS REQUIRED BY SEC. R320 FBC-RESIDENTIAL. NOTE: IT
 LOOKS LIKE THE MASTER BATHROOM IS THE BATHROOM WITH
 MAXIMUM PRIVACY. THE DOOR SIZE SPECIFIED IN THIS
 BATHROOM DOESN'T PROVIDE A 29" CLEAR OPENING. REVISE AS
 REQUIRED.
  
 8- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 BY SEC. R807 FBC-RESIDENTIAL.
  
 9-PROVIDE SPECIFICATIONS FOR GARAGE DOOR LEADING TO THE
 INTERIOR OF THE HOUSE SHOWING COMPLIANCE WITH THE FIRE
 RESISTANT REQUIREMENTS OF SEC. R302.5 FBC-RESIDENTIAL.
  
 10- ALUMINUM HINGED COLONIAL SHUTTER DETAILS ON SHEET
 A2. PROVIDE ATTACHMENT DETAIL/SPECIFICATIONS THAT MATCH
 PROPOSED INSTALLATION AND LOCATION. ALSO, CLARIFY IF
 THESE SHUTTERS ARE GOING TO BE FIXED OR OPERABLE.
 PROVIDE PRODUCT APPROVAL IF OPERABLE SHUTTERS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 11- TYPICAL 1 STORY WALL SECTION A/A3:
 A) ROOF SHEATHING NAILING SPECIFICATIONS ARE NOT CLEAR.
 REVISE AS REQUIRED. SEC. R803.2.3.1 FBC-RESIDENTIAL.
  
 B) REVISE "EXTERIOR FINISH GRADE NOTE". NEED 12" MIN
 NOT 8". SEC. R403.1.4 FBC-RESIDENTIAL.
 NOTE: REVISE DIMENSIONS ON EXTERIOR FOOTING
 ACCORDINGLY. NOTE: COORDINATE WITH SIZE OF FOOTING
 SHOWN ON SHEET S1.
  
 C) SHOW THE 6" CLEARANCE BETWEEN FINISH GRADE AND
 EXTERIOR WALL COVERING AS REQUIRED BY SEC. R318.7
 FBC-RESIDENTIAL. NOTE: COORDINATE WITH ITEM ABOVE.
  
 12- REVISE ALL WINDOWS AND DOORS STRUCTURAL BUCK
 DETAILS ON SHEET A3 TO COMPLY WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL. NOTE: BEVELED BUCKS ARE NOT ALLOWED
 AND STRUCTURAL BUCKS NEED TO PROVIDE FULL SUPPORT TO
 THE DOOR AND WINDOW FRAME.
  
 13- FOUNDATION PLAN SHOWN ON SHEET S1 AND FLOOR PLAN
 SHOWN ON SHEET A1 DON'T MATCH. REVISE AS REQUIRED.
 NOTE: LAYOUT OF BATHROOMS DON'T MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 14- ROOF SHEATHING SPECIFICATIONS ON "ROOF SHEATHING
 NOTE", "DIAPHRAGM SCHEDULE", "NAILING ZONES" AND
 ""FASTENER SCHEDULE" ON SAME SHEET S2 DON'T MATCH.
 REVISE AS REQUIRED TO MATCH. SEE SEC. R803.2.3.1
 FBC-RESIDENTIAL AND REVISE AS REQUIRED TO MATCH.
  
 15- REVISE "DEPT. PRODUCT SUBMITTAL AFFIDAVIT" ON SHEET
 CVR. COORDINATE PRODUCT APPROVAL OR NOA WITH ONES
 SUBMITTED. CLARIFY/REVISE THE "ATTACHMENT METHOD
 REQUIRED TO MAKE SURE IT APPLIES TO SPECIFIC PRODUCT.
 CHECK EXPIRATION DATES, ETC. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 16- ENGINEER OF RECORD TO SPECIFY INSULATION BETWEEN
 GARAGE AREA AND A/C AREA AS REQUIRED BY SEC. R103.2
 FBC-ENERGY CONSERVATION. NOTE: COORDINATE WITH THE
 ENERGY CALCULATION TO AVOID CONFLICTS/DELAYS.
  
 17- ENERGY CALCULATIONS SUBMITTED:
 A)THE BUILDING?S OWNER, THE OWNER?S ARCHITECT OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE PRIOR TO RECEIVING THE PERMIT AS REQUIRED BY SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C) REVISE ITEM #9(A). THE EXTERIOR WALL INSULATION
 DOESN'T MATCH PLANS. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) REVISE ITEM #9(B). THE MATERIAL OF ADJACENT WALL
 FRAME IS NOT WOOD. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)REVISE DOORS INFORMATION TO MATCH PLANS AND PRODUCT
 APPROVALS SUBMITTED. WHICH ONE IS THE INSULATED DOOR
 AND WHICH ONE IS THE WOOD DOOR? ALSO, SEE PLANS FOR
 ORIENTATION OF DOORS. DOORS WITH GLAZING NEED TO BE
 CONSIDERED IN THE GLAZING AREA. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 F)WINDOWS FRAME MATERIAL DOESN'T MATCH PLANS AND
 PRODUCT APPROVALS SUBMITTED. REVISE AS REQUIRED TO
 MATCH. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G) PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THE
 U-FACTOR AND SHGC SPECIFIED ON ITEM #7 AS REQUIRED BY
 SEC. R405.4.3 FBC-ENERGY CONSERVATION.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 18- PRODUCT APPROVALS WILL BE REVIEWED ONCE THE DESIGN
 PRESSURES ARE CLARIFIED. SEE COMMENT #2 ABOVE. NOTE:
 ENGINEER OF RECROD TO REVIEW AND APPROVE THEM PRIOR TO
 SUBMITTAL.
  
 19- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $232,590. THE
 PERMIT FEE BALANCE IS $4618.61.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  