| Notes |
| Date |
Text |
| 2019-01-02 15:20:03 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | ROOFING PRODUCT APPROVAL FOR BALCONY NOA NO. 15-0707.04 | | | IS DENIED. | | | | | | 1) THE LIQUID APPLIED MEMBRANE ROOFING SYSTEM ON SHEET | | | 14 OF NOA NO. 15-0707.04 IS FOR AN INSULATED WOOD DECK. | | | THE PLANS DO NOT SPECIFY ANY INSULATION ON TOP OF THE | | | PLYWOOD AT THE BALCONY. SUBMIT PRODUCT APPROVALS THAT | | | CORRESPOND WITH THE PLANS OR REVISE THE PLANS. FBC | | | 107.2.1 | | | | | | 2) THE DESIGN PRESSURE FOR THE SYSTEM ON SHEET 14 IS | | | -60 PSF AND LIMITATION NUMBER 7 WHICH DOES NOT ALLOW | | | ANY INCREASE. SHEET S000 OF THE PLANS SPECIFIES THE | | | REQUIRED DESIGN PRESSURES AS -116 PSF IN ROOF ZONE 3 | | | AND -79 PSF IN ROOF ZONE 2. SUBMIT PRODUCT APPROVALS | | | WITH ADEQUATE DESIGN PRESSURES. |
|