2018-12-21 14:50:16RESIDENTIAL (R2) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLAT ROOF:
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) FOR PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION #7 OF NOA 16-1206.02 SUBMITTED. SEC.
 1609.1.1 FBC.
  
 2- CLAY TILE:
 PROVIDE PRODUCT APPROVAL (2 COPIES) FOR ADHESIVE THAT
 IS LISTED IN THE CLAY TILE NOA 15-0915.09 SUBMITTED AND
 CLEARLY MARK PADDY SIZE. NOA 15-1201.04 SUBMITTED FOR
 ADHESIVE RTA-1 IS NOT LISTED IN THE CLAY TILE NOA
 SUBMITTED.
 FAC 61G20-3.001.
  
 3-CLEARLY IDENTIFY WHICH ROOF TILE UNDERLAYMENT FROM
 NOA 17-0614.22 SUBMITTED IS GOING TO BE INSTALLED. SEC.
 107.2.1 CITY AMENDMENTS.
  
  
  