Plan Review Notes
Plan Review Notes For Permit 18120758
Permit Number 18120758
Review Stop B
Sequence Number 1
Notes
Date Text
2019-01-02 13:06:122017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18120758
 ADD: 250 S AUSTRALIAN AVE/ 17TH & 18TH FLOORS/ DEMO
 ONLY
 CONT: TURNER CONSTRUCTION
 TEL: 786-621-9000
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JAN. 02/2019
 ACTION: DENIED
  
 1) ON BOTH SHEETS FOR THE 17TH & 18TH FLOORS THERE IS A
 SPECIFIC DEMOLITION NOTE STATING ALL WALLS, DOOR AND
 FIXTURES SHOWN IN SOLID LINES ARE EXISTING TO REMAIN.
 THE AREA OF CONCERN IS THE ELEVATOR LOBBY FOR BOTH
 FLOORS. THERE IS NO NOTES STATING THAT THIS BUILDING
 HAS PRESSURIZED ELEVATOR SHAFTWAYS IN COMPLIANCE WITH
 THE 2017 FBC-B 3006.3 HOISTWAY OPENING PROTECTION. ONE
 OF 4 METHODS. YOU ARE REMOVING THE ENCLOSED ELEVATOR
 LOBBY.
  
 IN THE 2017 EXISTING BUILDING CODE SEE SECTION 803.2.2
 SUPPLEMENTAL SHAFT AND FLOOR OPENING ENCLOSURE
 REQUIREMENTS. WHERE THE WORK AREA ON ANY FLOOR EXCEEDS
 50 PERCENT OF THAT FLOOR AREA, THE ENCLOSURE
 REQUIREMENTS OF SECTION 803.2 SHALL APPLY TO VERTICAL
 OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE FLOOR.
  
 WITH THE REMOVAL OF THE ELEVATOR LOBBY A VIOLATION IS
 BEING CREATED. CREATION OR EXTENSION OF NONCONFORMITY.
 2017 EXISTING BUILDING CODE LEVEL II 801.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING. CREATION OR EXTENSION
 OF NONCONFORMITY. ALL NEW WORK, RE-CONFIGURATION SHALL
 NOT CREATE OR EXTEND ANY NONCONFORMITY IN THE EXISTING
 BUILDING TO WHICH THE RE-CONFIGURATION OF SPACE IS
 BEING MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL
 STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY
 OF MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 2) . A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  