| 2019-02-25 14:49:08 | 1) SHT. SP- 1.02 - A NOTE IN THE LOWER RIGHT HAND |
| | CORNER OF THE PLAN REFERS TO THE 2014 FLORIDA BUILDING. |
| | REVISE THE NOTE TO READ THE 2017 FLORIDA BUILDING CODE. |
| | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MDF |
| | SHOWER TOWER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 3) SHOW THE WIDTH OF THE POOL ON THE PLANS.THE |
| | DIMENSIONS ARE MISSING ON THE RIGHT SIDE OF THE POOL ON |
| | SHT. SP- 1.04.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) SHT. SP-1.05 - SHOW THE SPACING OF THE GUTTER DRAINS |
| | ON THE PLANS. SPACING SHALL CCOMPLY WITH 2017 FBC |
| | SEC.454.1.6.5.3.1. |
| | 5) SHT. SP-1.05 - SIZE THE GUTTER LINE TO THE COLLECTOR |
| | TANK. |
| | 6) SHT. SP-1.05 - SIZE THE RETURN LINE BRANCES INTO THE |
| | POOL. |
| | 7) SHT. SP-1.07 - DETAIL #10 CALLS OUT THE MAXIMUM FLOW |
| | FOR THE PARAMOUNT MAIN DRAIN AT 95 GPM @1.5 FPS AND THE |
| | MAIN DRAIN TABLE IN THE DETAIL SHOWS THE SAME PARAMOUNT |
| | DRAIN WITH A FLOW OF 200 GPM. CLARIFY. |
| | 8) SHT. SP-1.07 - THE MAIN DRAIN TABLE REFERS TO |
| | FLORIDA BUILDING CODE SEC. 424.1. THIS CODE SECTION IS |
| | FOR CHILDREN'S PLAY STRUCTURES AND IS OBVIOUSLY |
| | INCORRECT. REVISE THE NOTE WITH THE CORRECT CODE |
| | SECTION. |
| | 9) THE PLANS REFER TO THE DISCHARGE OF RAINWATER TO THE |
| | SANITARY ( SHT. SP-1.05) AND THE POOL MAINTENANCE LINE |
| | TO THE SANIRAY. STORMWATER AND THE POOL MAINTENACE LIN |
| | CANNOT DRAIN TO THE SANITARY SYSTEM PER CITY ORDINANCE |
| | ARTICLE III, SEC. 90-126 (B) (5). PLEASE CONTACT MANNY |
| | GONZALEZ IN THE CITY OF WEST PALM BEACH ENGINEERING |
| | DEPT. FOR FURTHER DIRECTION. 561-494-.1040. |
| | 10) SHT. SP-1.08 - DETAIL # 1 - PLACE A NOTE ON THIS |
| | SHEET THAT THE LEGEND FOR THE SHOWN ITEMS IS LOCATED ON |
| | SHT. SP-2.04. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 11) SUBMIT VERIFICATION THAT THE MAXIMUM FILTRATION |
| | RATE IN GALLONS PER MINUTE PER SQUARE FOOT OF FILTER |
| | AREA OF 0.375 FOR CARTRIDGE FILTERS IS NOT EXCEEDED PER |
| | 2017 FBC SEC.454.1.6.5.5.1 |
| | 12) SHT. SP-1.08 - THE PLANS REFER TO NSF-50, 2007. THE |
| | REFERENCED EDITION IN THE FBC IS THE 2011 EDITION. |
| | PLEASE REVISE THE NOTE. |
| | 13) SHT. SP-1.08 - THE POOL HEATER SHALL HAVE A MINIMUM |
| | THERMAL EFFICIENCY OF 82% PER THE 2017 FBC-ENERGY, |
| | TABLE C404.2. |
| | 14) SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF |
| | VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE |
| | THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER |
| | 2017 FBC-FUEL GAS SECS. 502 THRU 505. |
| | 15) PLACE THE SPECIFIC ADDRESS OF THIS PROJECT ON ALL |
| | PLAN SHEETS AND THE APPLICATION.FL. STATUTE 713.135. |
| | 16) SHT. SP-1.08 - DETAIL #6 - THE PLANS READ" SEE MEP |
| | PLANS FOR FLUE TERMINATION." WHAT MEP PLANS? CLARIFY. |
| | 17) ALL HOSE BIBBS SHALL BE EQUIPPED WITH A SEPARATE |
| | SHUTOFF VALVE PER 2017 FBC-PLUMBING SEC. 606.2. |
| | 18) SHT. SP-2.04 - LEVEL 5 SWIMMING POOL LEGEND - NOTES |
| | "F" & "H" - REFER TO THE DISCHARGE OF RAINWATER AND THE |
| | POOL MAINTENANCE LINE TO THE SANITARY SEWER. STORMWATER |
| | AND THE POOL MAINTENACE LIN CANNOT DRAIN TO THE |
| | SANITARY SYSTEM PER CITY ORDINANCE ARTICLE III, SEC. |
| | 90-126 (B) (5). PLEASE CONTACT MANNY GONZALEZ IN THE |
| | CITY OF WEST PALM BEACH ENGINEERING DEPT. FOR FURTHER |
| | DIRECTION. 561-494-.1040. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |