| 2019-01-10 15:42:22 | CODES IN EFFECT: |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 5TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: DENIED |
| | |
| | 1. RE: PLAN SHEET 101.0; TYPICAL SHOWER DETAILS. THE |
| | DETAIL SHOWER PAN AND CURB DETAIL SHALL SHOW COMPLIANCE |
| | WITH FBC PL SECTION 417 INCLUDING THE REQUIRED 2% PITCH |
| | REQUIRED FOR THE MEMBRANE PER WPB FBC 107.2.1. SHOW |
| | TYPE OF MATERIAL OF SHOWER DRAIN PIPE. PROVIDE ASSEMBLY |
| | HAVING A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR |
| | TO BE USED FOR DEALING WITH THE SHOWER FLOOR |
| | PENETRATION AND THE ELIMINATED TUB DRAIN OPENING AS |
| | REQUIRED BY FBC 714.4.1 THROUGH 714.4.4.1.2 PER WPB FPC |
| | 107.2.1. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |