| 2019-02-11 15:14:17 | ** FAILED ** |
| | |
| | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE |
| | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE |
| | APPLICABLE: |
| | |
| | 1.) SURVEY OF THE PROPERTY IS MISSING FROM THE PERMIT |
| | APPLICATION. PLEASE PROVIDE AN UPDATED, SIGNED AND |
| | SEALED SURVEY OF THE PROPERTY. |
| | |
| | 2.) SITE PLAN MUST BE CONSISTENT WITH THE FEATURES IN |
| | THE SURVEY OF THE PROPERTY. PROPERTY LINES AND SETBACK |
| | DIMENSIONS SHALL ALSO BE CLEARLY PROVIDED IN THE SITE |
| | PLAN. |
| | |
| | 3.) SITE PLAN SHOWS AN ENTRANCE GATE WITH NO PERIMETER |
| | WALL. IS A WALL PROPOSED? IF SO, DETAILS WILL NEED TO |
| | BE PROVIDED IN THE SITE PLAN. |
| | |
| | 4.) ENTRANCE GATE ALONG EAST LAKEWOOD ROAD SHALL NOT |
| | EXCEED 6 FT. IN HEIGHT AS MEASURED FROM GRADE (FROM THE |
| | OUTSIDE WALL). PLEASE NOTE THAT THE HEIGHT INCLUDES ANY |
| | STRUCTURAL FEATURES (I.E. STEPS, ETC.) THE ENTRANCE |
| | WALL MAY SIT ON. [ZLDR S.94-302(B)] |
| | |
| | 5.) STEPS WHICH ARE 3 FT. OR LESS ABOVE GRADE MAY |
| | ENCROACH INTO ANY REQUIRED SETBACK AREA TO A POINT NO |
| | CLOSER THAN 2 FT. TO THE PROPERTY LINE. PROPOSED |
| | ENTRANCE GATE STEPS DO NOT SEEM TO MEET THIS ZONING |
| | REQUIREMENT. [ZLDR S.94-305(B)(7)] |
| | |
| | |
| | NOTES: |
| | |
| | * SCOPE OF WORK ($39,000.00) DOES NOT EXCEED 50% VALUE |
| | OF THE STRUCTURE PER 2018 PAPA IMPROVEMENT VALUE |
| | ($139,719). |
| | |
| | * REVISION MAY RESULT IN ADDITIONAL COMMENTS. |
| | |
| | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE |
| | QUESTIONS. |
| | |
| | * ZONE: SF14 |
| | |