Plan Review Notes
Plan Review Notes For Permit 18120675
Permit Number 18120675
Review Stop M
Sequence Number 3
Notes
Date Text
2019-04-24 15:21:53MECHANICAL PROVISOS:
  
 A REVISION TO THE PLAN IS REQUIRED:
  
 1) RELOCATE THE OUTSIDE AIR INTAKES A MINIMUM 10'
 HORIZONTALLY AWAY FROM THE PARKING LOT AND DRIVEWAYS.
  
 2) PROVIDE EQUIPMENT SCHEDULES AND SPECS FOR EXISTING
 AC SYSTEMS.
  
  