| 2019-03-14 12:04:22 | |
| | |
| | 2ND REVIEW: 18120675 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS:PREVIOUS COMMENTS 2ND REQUEST |
| | |
| | NOT COMPLIED 1. PLEASE SHOW DIMENSIONS ON THE CLEAR |
| | FLOOR SPACE FOR THE TOILET AND LAVATORY. PER FBC ACC |
| | 604.3.1, 606.2 |
| | |
| | NOT COMPLIED 4. MIRRORS LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. PER FBC ACC 603.3 |
| | |
| | PARCIALY COMPLIED 5. TOILET PAPER DISPENSERS SHALL |
| | COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 |
| | INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR. PER FBC ACC 604.7 |
| | HIEGHT DIMENSION IS NOT SHOWN. |
| | |
| | NOT COMPLIED 7. GRAB BARS SHALL BE INSTALLED IN A |
| | HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE. FBC ACC 609.4 |
| | |
| | NOT COMPLIED 8. THE WATER CLOSET SHALL BE POSITIONED |
| | WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE. |
| | THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| | MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION. PER FBC ACC 604.2 |
| | |
| | NOT COMPLIED 9. SHOW CLEAR FLOOR SPACE FOR THE BREAK |
| | ROOM SINK AND ONE OF THE EXAM ROOM SINKS WITH THE SPACE |
| | BEING CENTERED ON THE FIXTURE. PER FBC ACC 212.3 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |