Plan Review Notes
Plan Review Notes For Permit 18120675
Permit Number 18120675
Review Stop P
Sequence Number 2
Notes
Date Text
2019-03-14 12:04:22 
  
 2ND REVIEW: 18120675
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:PREVIOUS COMMENTS 2ND REQUEST
  
 NOT COMPLIED 1. PLEASE SHOW DIMENSIONS ON THE CLEAR
 FLOOR SPACE FOR THE TOILET AND LAVATORY. PER FBC ACC
 604.3.1, 606.2
  
 NOT COMPLIED 4. MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. PER FBC ACC 603.3
  
 PARCIALY COMPLIED 5. TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR. PER FBC ACC 604.7
 HIEGHT DIMENSION IS NOT SHOWN.
  
 NOT COMPLIED 7. GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE. FBC ACC 609.4
  
 NOT COMPLIED 8. THE WATER CLOSET SHALL BE POSITIONED
 WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE.
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION. PER FBC ACC 604.2
  
 NOT COMPLIED 9. SHOW CLEAR FLOOR SPACE FOR THE BREAK
 ROOM SINK AND ONE OF THE EXAM ROOM SINKS WITH THE SPACE
 BEING CENTERED ON THE FIXTURE. PER FBC ACC 212.3
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  