| Plan Review Notes For Permit 18120675 |
| Permit Number |
18120675 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-03-12 14:21:06 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING 2ND PLAN REVIEW (DENIED): | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. A. OK BY PROVISO (PROVIDE AT TIME OF INSPECTION). IT | | | APPEARS THAT THE INTERIOR TRIM IS NON COMBUSTIBLE. | | | PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATIONS FOR | | | THE ALUMINUM TRELLIS. | | | B. OK (NO FABRIC) | | | 5. OK | | | 6. FBC B 107.2.1.2 (FAIL) SHEET A3-02 DOES NOT MATCH | | | THE OTHER PAGES. | | | 7. A. OK THE PRODUCT APPROVALS FOR THE LOUVERS AND ROOF | | | TOP VENTILATORS WERE SUBMITTED BUT NEED TO BE APPROVED | | | BY DESIGNER OF RECORD PER NOTE (7B) BELOW | | | B. OK BY PROVISO FL ADMIN. RULES FL 61G1-23.015 THE | | | DESIGNER OF RECORD NEEDS TO REVIEW AND STAMP THE | | | PRODUCT APPROVALS. | | | C. OK BY PROVISO THE DESIGNER OF RECORD NEEDS TO REVIEW | | | AND STAMP THE PRODUCT APPROVALS. | | | 8. FBC B 107 (FAIL) THIS ITEM HAS NOT BEEN ADDRESSED. | | | 9. OK |
|