Plan Review Notes
Plan Review Notes For Permit 18120675
Permit Number 18120675
Review Stop B
Sequence Number 2
Notes
Date Text
2019-03-12 14:21:06****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING 2ND PLAN REVIEW (DENIED):
  
 1. OK
 2. OK
 3. OK
 4. A. OK BY PROVISO (PROVIDE AT TIME OF INSPECTION). IT
 APPEARS THAT THE INTERIOR TRIM IS NON COMBUSTIBLE.
 PLEASE PROVIDE THE MANUFACTURER'S SPECIFICATIONS FOR
 THE ALUMINUM TRELLIS.
 B. OK (NO FABRIC)
 5. OK
 6. FBC B 107.2.1.2 (FAIL) SHEET A3-02 DOES NOT MATCH
 THE OTHER PAGES.
 7. A. OK THE PRODUCT APPROVALS FOR THE LOUVERS AND ROOF
 TOP VENTILATORS WERE SUBMITTED BUT NEED TO BE APPROVED
 BY DESIGNER OF RECORD PER NOTE (7B) BELOW
 B. OK BY PROVISO FL ADMIN. RULES FL 61G1-23.015 THE
 DESIGNER OF RECORD NEEDS TO REVIEW AND STAMP THE
 PRODUCT APPROVALS.
 C. OK BY PROVISO THE DESIGNER OF RECORD NEEDS TO REVIEW
 AND STAMP THE PRODUCT APPROVALS.
 8. FBC B 107 (FAIL) THIS ITEM HAS NOT BEEN ADDRESSED.
 9. OK