| 2019-01-24 18:10:04 | |
| | |
| | 1ST REVIEW: 18120675 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE SHOW DIMENSIONS ON THE CLEAR FLOOR SPACE FOR |
| | THE TOILET AND LAVATORY. PER FBC ACC 604.3.1, 606.2 |
| | |
| | 1. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH |
| | FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM |
| | MEASURED TO THE TOP OF THE SEAT.PER FBC ACC 604.4 |
| | |
| | 2. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| | MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL |
| | AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. PER |
| | FBC ACC 604.5.1 |
| | |
| | 3. THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES (610 |
| | MM) MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2 |
| | |
| | 4. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| | SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| | REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND. PER FBC ACC 603.3 |
| | |
| | 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT |
| | OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE |
| | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 |
| | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR. PER FBC ACC 604.7 |
| | |
| | 6. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE |
| | FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER |
| | FBC ACC 606.3 |
| | |
| | 7. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES MINIMUM AND 36 INCHES MAXIMUM ABOVE |
| | THE FINISH FLOOR MEASURED TO THE TOP OF THE GRIPPING |
| | SURFACE. FBC ACC 609.4 |
| | |
| | 8. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR |
| | PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE |
| | OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18 |
| | INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION. PER FBC |
| | ACC 604.2 |
| | |
| | 9. SHOW CLEAR FLOOR SPACE FOR THE BREAK ROOM SINK AND |
| | ONE OF THE EXAM ROOM SINKS WITH THE SPACE BEING |
| | CENTERED ON THE FIXTURE. PER FBC ACC 212.3 |
| | |
| | 10. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS FOR THE |
| | REMOTE CHILLER. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 11. SHOW SHUT OF VALVES ON THE RISER FOR ALL THE DROPS |
| | PER FBC PL 212.3 (5) |
| | |
| | 12. IF NEW BACKFLOW IS INSTALLED AT METER A SEPARATE |
| | PERMIT WILL BE REQUIRED A NOTE ON THE PLAN WILL |
| | SUFFICE. PER WPB UTILITIES DEPT. |
| | |
| | 13.NOTE ON PLAN WHAT TYPE OF ANCHORS ARE TO BE USED FOR |
| | THE WATER HEATER BRACKET TO HOLD A MIN OF 500LB. PER |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |