2019-01-18 16:44:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18120675
 1/18/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1: CLARIFY THE NEED TO HAVE EXHAUST
 VENTILATION IN THE RETAIL AREA, AND PROVIDE AN EXHAUST
 VENTILATION CALCULATION TO SHOW HOW EF-6 WAS SIZED-
 SECTION 403.3 FBC M.
  
 2) M1 & M3: 420 CFMS OF EXHAUST IS SHOWN IN THE AIR
 BALANCE CALC AS THE VENTILATION REQUIRED RATE FOR THE
 RETAIL AREA, HOWEVER THE SCHEDULE INDICATES A FAN WITH
 A CAPACITY OF 1395 CFMS. CLARIFY THE NEED FOR SUCH A
 LARGE FAN- SECTION 107.2.1 WPB.
  
 3) REFER TO SECTION C403.2.7 FBC EC AND PROVIDE AN
 ENERGY RECOVERY VENTILATOR FOR THE EF-6/AHU-5 SYSTEM.
  
 4) SUBMIT FL. PRODUCT APPROVALS OR MIAMI-DADE NOA'S FOR
 THE LOUVERS AND GRAVITY VENTILATORS- RULE 9N-3 FAC.
  
 5) INDICATE THE TYPE OF EXISTING DOORS THAT ARE
 ENCLOSING THE AIR HANDLER CLOSETS- SEE SECTION 602.2
 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  