| Plan Review Notes For Permit 18120672 |
| Permit Number |
18120672 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-01-07 10:53:12 | PLAN DENIED | | | 1) PLEASE SHOW DUCT WORK ON AIR CONDITIONING PLAN | | | SHOWING DUCT SIZE AND OUTSIDE AIR DUCT AND SIZE. | | | 2) NEW CONFERENCE ROOM SHOWS THREE SUPPLY DROPS | | | AND ONE RETURN. REFER TO SECTION 601.6 BALANCED RETURN | | | AIR | | | 2017 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 | | | |
|