| | 1ST REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. RE: PLAN SHEET A2.0; KITCHENETTE |
| | A. TAG R19-SINK: SINK SHALL COMPLY WITH THE |
| | REQUIREMENTS OF FBC ACC SECTION 606 PER FBC ACC 212.3; |
| | PLANS SHALL PROVIDE THE APPROPRIATE INFORMATION SHOWING |
| | COMPLIANCE PER WPB FBC 107.2.1.PROVIDE SPECIFICATION |
| | FOR SINK PER WPB FBC 107.2.1. |
| | B. TAG R15-WATER DISPENSER: ON PLUMBING PLAN SHEET |
| | P1.1, THERE IS NO PROVISION FOR WATER SUPPLY TO THE |
| | WATER DISPENSER OR WASTE. PROVIDE THE APPROPRIATE |
| | INFORMATION ON THE PLANS, INCLUDING ANY REQUIREMENTS |
| | FOR BACKFLOW PREVENTION AS OUTLINED IN FBC PL SECTION |
| | 608 AND PROVIDE SPECIFICATION FOR WATER DISPENSER PER |
| | WPB FBC 107.2.1. |
| | 2. RE: PLAN SHEET P1.1; DETAIL #1 SPECIFIES 3/4" HOT |
| | WATER TO FIXTURES AND RISER #2 SPECIFIES 1/2" HOT |
| | WATER. PLEASE CLARIFY PER WPB FBC 107.2.1 |
| | 3. RE: PLAN SHEET A0; THE RENOVATION IS TAKING PLACE IN |
| | A 12,000+ SQ FT FACILITY FACTORY (F) OCCUPANCY. THE |
| | EXISTING PLUMBING COUNT NOTES BATHROOM FIXTURES AND THE |
| | EXISTING BATHROOMS ARE LOCATED ON PLAN SHEET D1 FLOOR |
| | PLANS;THERE IS NO INDICATION OF A SERVICE SINK OR A |
| | DRINKING FOUNTAIN AS REQUIRED BY FPC PL TABLE 403.1. |
| | P:LEASE CLARIFY PER WPB FBC 107.2.1. |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |