Plan Review Notes
Plan Review Notes For Permit 18120642
Permit Number 18120642
Review Stop ENG
Sequence Number 2
Notes
Date Text
2019-02-08 15:21:16CITY OF WEST PALM BEACH CODE OF ORDINANCES, SECTION
 94-35, SITE PLAN REVIEW
  
 (C) SITE DESIGN QUALITATIVE DEVELOPMENT STANDARDS.
 (11) STORMWATER CONTROL. APPROPRIATE MEASURES SHALL BE
 TAKEN TO ENSURE THAT REMOVAL OF STORMWATER WILL NOT
 ADVERSELY AFFECT NEIGHBORING PROPERTIES OR THE PUBLIC
 STORM DRAINAGE SYSTEM. PROVISIONS SHALL BE MADE FOR THE
 CONSTRUCTION OF FACILITIES, INCLUDING GRADING, GUTTERS,
 PIPING AND THE TREATMENT OF TURF, TO ACCOMMODATE
 STORMWATER AND TO PREVENT EROSION AND THE FORMATION OF
 SILT.
  
 WATER QUALITY CRITERIA
 RETENTION/DETENTION REQUIREMENTS
 1. VOLUME IS CALCULATED AS:
 WET DETENTION VOLUME SHALL BE PROVIDED FOR THE FIRST
 INCH OF RUNOFF FROM THE DEVELOPED PROJECT, OR THE TOTAL
 RUNOFF OF 2.5-INCHES TIMES THE PERCENTAGE OF
 IMPERVIOUSNESS, WHICHEVER IS GREATER,
  
 FOR ANY RECONSTRUCTION OF A PARKING LOT, THE OWNER
 SHOULD INSTALL A DRAINAGE SYSTEM TO PROVIDE WATER
 QUALITY TREATMENT OF THE STORMWATER RUNOFF, WHETHER IT
 BE PERVIOUS PAVERS, AN EXFILTRATION TRENCH, OR
 BIOSWALE.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
  
 DIRECT: (561) 818-1322
  
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  