2019-01-31 10:51:07****CORRECTIONS****
 W.P.B. PERMIT: 18120609
 REVIEWED: JANUARY 31, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1. 501 FBC[EXISTING] STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED.
  -PLEASE ADD LEVEL OF ALTERATION TO DESIGN DATA. THIS
 LOOKS LIKE ADDITION AND LEVEL 3 ALTERATION SINCE MORE
 THAN 50% AFFECTED AREA.
  
 2. 301.4 FBC[R] DEAD LOAD. THE ACTUAL WEIGHTS OF
 MATERIALS AND CONSTRUCTION SHALL BE USED FOR
 DETERMINING DEAD LOAD WITH CONSIDERATION FOR THE DEAD
 LOAD OF FIXED SERVICE EQUIPMENT.
  
 3. R301.5 FBC[R] LIVE LOAD. THE MINIMUM UNIFORMLY
 DISTRIBUTED LIVE LOAD SHALL BE AS PROVIDED IN TABLE
 R301.5.
  
 4. R301.6 FBC[R] ROOF LOAD. THE ROOF SHALL BE DESIGNED
 FOR THE LIVE LOAD INDICATED IN TABLE R301.6
  -PLEASE PROVIDE LIVE AND DEAD LOADS TO DESIGN DATA.
  
 5. 107.5.3 FBC[AMENDED] SHEETS REFER TO SEE STRUCTURAL,
 BUT THERE ARE NO STRUCTURAL SHEET(S). IS THERE A
 STRUCTURAL SHEET TO SHOW FOOTER SIZES, LOADS AND SLAB
 DETAILS?
 A. 506.2.3 FBC[R] VAPOR RETARDER. A 6-MIL (0.006 INCH)
 POLYETHYLENE OR APPROVED VAPOR RETARDER WITH JOINTS
 LAPPED NOT LESS THAN 6 INCHES (152 MM) SHALL BE PLACED
 BETWEEN THE CONCRETE FLOOR SLAB AND THE BASE COURSE OR
 THE PREPARED SUBGRADE WHERE NO BASE COURSE EXISTS.
 EXCEPTION: THE VAPOR RETARDER IS NOT REQUIRED FOR THE
 FOLLOWING:
 B. 318.1 FBC[R] TERMITE PROTECTION. TERMITE PROTECTION
 SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING
 SOIL APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER APPROVED METHODS
 OF TERMITE PROTECTION LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE SECTION 202,
 ?REGISTERED TERMITICIDE.? UPON COMPLETION OF THE
 APPLICATION OF THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE ISSUED TO THE
 BUILDING DEPARTMENT BY THE LICENSED PEST CONTROL
 COMPANY THAT CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE
 PREVENTION OF SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS ESTABLISHED BY THE
 FLORIDA DEPARTMENT OF AGRICULTURE AND CONSUMER
 SERVICES.?
 C. 506.2.4.2 FBC[R] CRACK CONTAINMENT MEASURES
 COMPLYING WITH ONE OF THE FOLLOWING: SEE 506.2.4.2
  
  
 6. 301.2.1 FBC[R] PROVIDE DESIGN PRESSURES NEEDED FOR
 WINDOWS, DOORS, GARAGE DOOR, CLADDING AND COMPONENTS.
  
 7. 301.2.1.2 FBC[R] PROTECTION OF OPENINGS.
  -PROVIDE NOTES/DETAILS FOR PROTECTION FROM WINDBORNE
 DEBRIS TO ALL EXTERIOR OPENINGS INCLUDING WINDOWS,
 ENTRY DOORS AND GARAGE DOORS.
  
 8. 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL, DOORS AND SLIDERS, OR INDICATE
 THAT YOU WOULD LIKE THEM DEFERED.
  -NUMBERS ARE LISTED ON SHEET A-003. IF THOSE THE
 PRODUCT APPROVALS PLEASE PROVIDE TWO COPIES OF EACH.
  
 9. 302.10 FBC[R] PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
 A. IS THE WHOLE ATTIC GETTING NEW SPRAY INSULATION?
 B. WILL THE WHOLE ATTIC BE UNVENTED AS STATED IN ENERGY
 CALCULATIONS?
 C. PLEASE MAKE SURE THE ENERGY CALCULATIONS MATCH THE
 INSULATION, VENTING AND TYPE BEING PROVIDED AND HAVE
 THE OWNER OR AGENT SIGN THE ENERGY CALCULATION BELOW
 WHERE THE PREPARER SIGNED. (CURRENTLY THE ENERGGY CALCS
 SHOW BLOWN IN INSULATION)
  
 10. 806 FBC[R] SUPPLY VENTING CALCULATIONS FOR THE
 ATTIC AND HOW THE AREA OF VENTING WILL BE ACHIEVED, OR
 FOLLOW R805.5 FOR UNVENTED.
  
 11. 807 FBC[R] BUILDINGS WITH COMBUSTIBLE CEILING OR
 ROOF CONSTRUCTION SHALL HAVE AN ATTIC ACCESS OPENING TO
 ATTIC AREAS THAT HAVE A VERTICAL HEIGHT OF 30 INCHES
 (762 MM) OR GREATER OVER AN AREA OF NOT LESS THAN 30
 SQUARE FEET (2.8 M2).
  -SHOW ATTIC ACCESS ON PLANS
  
 12. 315.1 FBC[R] CARBON MONOXIDE PROTECTION. EVERY
 SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, **AN ATTACHED GARAGE**, OR
 OTHER FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON
 MONOXIDE AS BYPRODUCT OF COMBUSTION SHALL HAVE AN
 OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10
 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES.
 EXCEPTION: THIS SECTION SHALL NOT APPLY TO EXISTING
 BUILDINGS THAT ARE UNDERGOING ALTERATIONS OR REPAIR
 UNLESS THE ALTERATION IS AN ADDITION AS DEFINED IN
 SECTION R315.1.3.
  
 13. 315.1.1 FBC[R] CARBON MONOXIDE ALARM. THE
 REQUIREMENTS OF SECTION R315.1 SHALL BE SATISFIED BY
 PROVIDING FOR ONE OF THE FOLLOWING ALARM INSTALLATIONS:
 1. A HARD-WIRED CARBON MONOXIDE ALARM.
 2. A BATTERY-POWERED CARBON MONOXIDE ALARM.
 3. A HARD-WIRED COMBINATION CARBON MONOXIDE AND SMOKE
 ALARM.
 4. A BATTERY-POWERED COMBINATION CARBON MONOXIDE AND
 SMOKE ALARM.
  
 14. 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS
 FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM
 DEFERED.
  
 15. 107.3.4.1 FBC[AMENDED] SUBMIT TRUSS SHOP DRAWINGS
 TO THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
  -THE TRUSS SUBMITTAL CAN BE APPROVED NOW IF PUT IN
 SUPPORTING DOCUMENTS AS A SUBMITTAL, OR IT CAN BE
 DEFERRED. IF DEFERED THE TRUSS PACKAGE NEEDS TO BE
 REVIEWED BY BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  