| Plan Review Notes For Permit 18120601 |
| Permit Number |
18120601 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-12-21 16:23:53 | BUILDING PLAN REVIEW | | | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | | | | JOSEAN A. DUPREY | | | PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | TEL: 561-805-6716 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | | BELOW. | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. ONE COPY OF EACH DRAWING SHEET WAS SUBMITTED. PLEASE | | | SUBMITT A MINIMUN OF 2 COPIES OF EACH DRAWING PAGE. FBC | | | 107 | | | | | | 2. APPLICATION WAS SUBMITTED AS A SUBMITTAL BUT WAS | | | CHANGE TO A REVISION OF PREVIOUS SUBMITTED DRAWINGS OF | | | PERMIT #17081077. | | | | | | 3. DETAILS 01 AND 02 ON S-200 TAGS DO NOT CORRESPOND TO | | | THE DETAILS PRESENTED ON PAGE S200. PLEASE CORRECT IT. | | | FBC 107 | | | | | | 4. NOTE FOR BEAM WB6 APPEARS TO MISTAKENLY CALL OUT | | | WB4. PLEASE CONFIRM. | | | | | | 5. THE DRAWING SHEET S200 CALLS FOR A REVISION 3 BUT | | | INFORMATION WAS NOT PROVIDED. PLEASE CONFIRM IF ANY | | | CHANGE WAS MADE. FBC 107 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED AND MARK VOID. |
|