| 2019-01-03 06:00:30 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. CONTRACTOR STATES THIS IS A 3-PHASE SERVICE BUT ONLY |
| | SHOWS 3 CONDUCTORS FROM METER-CAN TO ATS. GROUNDED |
| | CONDUCTOR MUST BE BROUGHT TO SERVICE ENTRANCE |
| | EQUIPMENT/DISCONNECTING MEANS. NEC 250.24C 230.41, |
| | 230.42 |
| | |
| | 2. ONE COPY OF PLANS SHOWS 3 PHASE CONDUCTORS TO 200 |
| | AMP PANEL PLUS AN EGC THE OTHER PLAN SHOWS 4 PHASE |
| | CONDUCTORS PLUS EGC. NEC 230.41, 230.42 |
| | |
| | 3. GENERATOR SHOWS 3 PHASE CONDUCTORS PLUS EGC. |
| | GENERATOR IS NOT 3-PHASE? FBC 107.2.1 NEC 230.41, |
| | 230.42 |
| | |
| | 4. PROVIDE LOAD CALCULATION OF EXISTING SERVICE. NEC |
| | 220 |
| | |
| | 5. PROVIDE CUT SHEET FOR GENERATOR FOR PRODUCT |
| | APPROVAL. FBC 107.2.1 NEC 90.7, 110.2, 110.3B |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |