| 2018-12-21 06:41:36 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOTE ON PERMIT REVISION APPLICATION STATES THERE ARE |
| | 2 METERS ON THIS PROPERTY AND CUSTOMER HAS ELECTED TO |
| | ONLY DO THE 3-PHASE SERVICE, ORGINAL REVIEWED AND |
| | APPROVED PLAN SHOWS A 3-PHASE SERVICE WITH 5 METERS AND |
| | DISCONNECTS- 1X 100AMP, 4X 70AMPS. NO "EXISITNG" 200AMP |
| | PANEL IS SHOWN ON PREVIOUS APPROVED PLAN. PLEASE |
| | PROVIDE CLARIFICATION AND AN ACCURATE ONE-LINE DIAGRAM |
| | OF OF ACTUAL WORK TO BE PERFORMED, TO INCLUDE A LOAD |
| | CALCULATION FOR SERVICE AND EXISITNG PANELS. FBC |
| | 107.2.1 NEC 220. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |