Plan Review Notes
Plan Review Notes For Permit 18120538
Permit Number 18120538
Review Stop B
Sequence Number 1
Notes
Date Text
2019-01-23 08:40:49****CORRECTIONS****
 PLAN REVIEW IN PROGESS
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, CHANGES MADE ARE NOT CLEAR. IN COMPARING
 WITH THE ISSUED PERMIT DOCUMENTS, IT APPEARS THAT THE
 DELTA DATE WAS CHANGED BUT NO ADDITIONAL CHANGES MADE
 ON MOST SHEETS. SOME PAGES APPEAR TO BE NEW, BUT
 NOTHING ON THE PAGE INDICATES THAT THEY ARE NEW SHEETS.
 THE NARRATIVE DESCRIBES CHANGES WHICH I WAS UNABLE TO
 LOCATE.
  
 A. FBC 107, REMOVE PAGES WHICH WERE NOT REVISED.
  
 B. REVISE NARRATIVE TO ACCURATELY DESCRIBE CHANGES MADE
 TO THE PLAN.
  
 C. ANY NEW SHEETS SHOULD HAVE A CLOUD AROUND THE SHEET,
 DELTA TO STATE "NEW SHEET".
  
 D. OTHER CHANGES SHOULD BE SHOWN WITH CLOUDS AND A
 DELTA 2 FOR ALL PAGES WHICH WERE ISSUED WITH A DELTA 1.
  
 2. FBC B 703.2, SHEETS A9.2, A9.3, PENETRATION AND
 FIRESTOPPING DETAILS WERE PROVIDED, SOME WITH THE TITLE
 "ENGINEERING JUDGEMENT FIRESTOP DETAIL".
  
 A. PER FS471, REVISE LANGUAGE OR HAVE PAGES PREPARED,
 SIGNED AND SEALED BY AN ENGINEER (PER FLORIDA STATUTE,
 AN ARCHITECT CANNOT USE THE WORD "ENGINEERING").
  
 B. SEE FBC B 703.2, FBC B 714.3,1.1, 714.4.1.2, TESTED
 ASSEMBLIES ARE REQUIRED (APPLICABLE TO ALL DETAILS
 WHICH ARE NOT TESTED ASSEMBLIES). FBC 104.11,
 ALTERNATIVE MATERIALS, DESIGN AND METHODS CAN BE
 PROPOSED AND ARE TO BE APPROVED BY THE BUILDING
 OFFICIAL. AN ALTERNATIVE MATERIAL, DESIGN OR METHOD OF
 CONSTRUCTION SHALL BE APPROVED WHERE THE BUILDING
 OFFICIAL FINDS THAT THE PROPOSED DESIGN IS SATISFACTORY
 AND COMPLIES WITH THE INTENT OF THE PROVISIONS OF THIS
 CODE, AND THAT THE MATERIAL, METHOD OR WORK OFFERED IS,
 FOR THE PURPOSE INTENDED, AT LEAST THE EQUIVALENT OF
 THAT PRESCRIBED IN THIS CODE IN QUALITY, STRENGTH,
 EFFECTIVENESS, FIRE RESISTANCE, DURABILITY AND SAFETY.
  
 SEE FBC 1044.11.1 AND .2 FOR DOCUMENTS REQUIRED:
  
 WHEN ALTERNATE LIFE SAFETY SYSTEMS ARE DESIGNED, THE
 SFPE ENGINEERING GUIDE TO PERFORMANCE-
 BASED FIRE PROTECTION ANALYSIS AND DESIGN OF BUILDINGS,
 OR OTHER METHODS APPROVED BY THE
 BUILDING OFFICIAL MAY BE USED. THE BUILDING OFFICIAL
 SHALL REQUIRE THAT SUFFICIENT EVIDENCE OR PROOF
 BE SUBMITTED TO SUBSTANTIATE ANY CLAIM MADE REGARDING
 THE ALTERNATIVE.
 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE
 NECESSARY TO ASSIST IN THE APPROVAL
 OF MATERIALS OR ASSEMBLIES NOT SPECIFICALLY PROVIDED
 FOR IN THIS CODE, SHALL CONSIST OF VALID
 RESEARCH REPORTS FROM APPROVED SOURCES.
 104.11.2 TESTS. WHENEVER THERE IS INSUFFICIENT EVIDENCE
 OF COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE, OR EVIDENCE THAT A MATERIAL OR METHOD
 DOES NOT CONFORM TO THE REQUIREMENTS
 OF THIS CODE, OR IN ORDER TO SUBSTANTIATE CLAIMS FOR
 ALTERNATIVE MATERIALS OR METHODS, THE
 BUILDING OFFICIAL SHALL HAVE THE AUTHORITY TO REQUIRE
 TESTS AS EVIDENCE OF COMPLIANCE TO BE
 MADE AT NO EXPENSE TO THE JURISDICTION. TEST METHODS
 SHALL BE AS SPECIFIED IN THIS CODE OR
 BY OTHER RECOGNIZED TEST STANDARDS. IN THE ABSENCE OF
 RECOGNIZED AND ACCEPTED TEST
 METHODS, THE BUILDING OFFICIAL SHALL APPROVE THE
 TESTING PROCEDURES. TESTS SHALL BE PERFORMED
 BY AN APPROVED AGENCY. REPORTS OF SUCH TESTS SHALL BE
 RETAINED BY THE BUILDING OFFICIAL FOR
 THE PERIOD REQUIRED FOR RETENTION OF PUBLIC RECORDS.
  
  
  
  
  
  
  