| 2019-01-02 10:19:33 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18120488 |
| | 1/2/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A FRONT ELEVATION VIEW OF THE HOOD AND |
| | COOKING APPLIANCES SHOWING THE REQUIRED CLEARANCES AS |
| | REQUIRED BY SECTION 507.4.1 FBC M. |
| | |
| | 2) CLARIFY IF THE COOKING APPLIANCES UNDER THE HOOD ARE |
| | NEW OR EXISTING. PLEASE NOTE A SEPARATE PERMIT WILL BE |
| | REQUIRED FOR INSTALLATION OF ALL NEW APPLIANCES. |
| | |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE FACTORY-BUILT GREASE |
| | DUCT IN ACCORDANCE WITH THE ENGINEER'S RECOMMENDATIONS |
| | ON SHEET #2- SEE SECTIONS 506.3.1.1 AND 506.3.11.3 FBC |
| | M. INDICATE THE MINIMUM CLEARANCE ALLOWED FROM THE |
| | GREASE DUCT TO THE COMBUSTIBLE ROOF MATERIALS. |
| | |
| | 4) PROVIDE STRUCTURAL DETAILS FOR THE NEW ROOF OPENING |
| | AND THE GURARD RAIL CONSTRUCTION- "BY OTHERS" IS NOT |
| | ACCEPTABLE FOR PERMITTING- PROVIDE ENGINEERED DRAWINGS |
| | AND A SUBPERMIT APPLICATION- SECTION 107.2.1 WPB. |
| | |
| | 5) PROVIDE A ROOF PLAN THAT SHOWS THE LOCATIONS OF THE |
| | FANS AND THE GUARD RAIL, AND THE FULL RUN LENGTH OF THE |
| | RAIL PER SECTION 304.11 FBC M. |
| | |
| | 6) REFER TO SECTION 508.1.1 FBC M AND SHOW COMPLIANCE. |
| | MAKEUP AIR TEMPERATURE. |
| | |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F |
| | (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS |
| | OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE |
| | HVAC SYSTEM. |
| | |
| | 7) SUBMIT THE NOA'S FOR THE FANS LISTED ON SHEET #4 |
| | |
| | 8) THE $11,000 JOB VALUE LISTED ON THE APPLICATION |
| | APPEARS LOW FOR THE ENTIRE SCOPE OF WORK. PLEASE |
| | PROVIDE COPIES OF CONTRACTS, INVOICES ETC. TO VERIFY |
| | ACCURATE VALUE- SECTION 109.3. PLEASE NOTE THAT VALUE |
| | IS BASED ON LABOR, MATERIALS, EQUIPMENT, SITE WORK, |
| | DESIGN FEES, AND OVERHEAD AND PROFIT. |
| | |
| | 9) COPIED ENGINEER'S SEALS AND SIGNATURES ARE NOT |
| | ACCEPTABLE PER SECTION 61G15-23.002 FAC. PLEASE PROVIDE |
| | ORIGNAL SIGNED AND SEALED PLANS. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |