| 2019-01-04 06:48:46 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ACCURATE LOAD CALCULATION AND PANEL |
| | SCHEDULE. PANEL SCHEDULE ISN'T LABELED CORRECTLY AND |
| | THERE WAS NO CLEAR LOAD CALCULATION PROVIDED. FBC |
| | 107.2.1 NEC 220, FBC RE E3602.2 NEC 210.8, 210.12, |
| | 215.5, 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902 |
| | |
| | 2. MINIMUM OF 2 SMALL APPLIANCE BRANCH CIRCUITS |
| | REQUIRED IN KITCHEN. NEC 210.11C1 |
| | |
| | 3, FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| | PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 |
| | |
| | 4. PROVIDE SPEC SHEET FOR WASHER/DRYER. 1, 2-POLE 30AMP |
| | BRANCH CIRCUIT DOESN'T SEEM FEASIBLE TO SUPPLY BOTH |
| | APPLIANCES. FBC 107.2.1 NEC 110.3B |
| | |
| | 5. WRONG BRANCH CIRCUIT CONDUCTOR SIZE AND OVERCURRENT |
| | PROTECTION SIZE FOR A 7KW WATER HEATER. PROVIDE |
| | CORRECTION. NEC 422.10, 422.11E, 422.13 |
| | |
| | 6. BONDING BRIDGE REQUIRED AT SERVICE NEC 250.94. |
| | |
| | 7. MINUMIM OF 2 GROUND RODS REQUIRED FOR GROUNDING |
| | ELECTRODE SYSTEM NEC 250.53A2 |
| | |
| | 8. RAISE VALUE. $5000 VALUE FOR A ENITRE HOUSE REMODEL |
| | AND SERVICE UPGRADE IS LOW. IF ACCURATE VALUE ISN'T |
| | GIVEN VALUE WILL BE SET BY BUILDING OFFICIAL. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |