| Plan Review Notes For Permit 18120461 |
| Permit Number |
18120461 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2019-01-04 16:35:02 | FAILED | | | | | | 1) EXTEND THE PHOTOMETRICS TO THE PROPERTY LINE TO THE | | | NORTH AND EAST OF THE GARAGE. THE ZONING CODE STATES, | | | "ANY SOURCE OF ILLUMINATION LOCATED WITHIN A COMMERCIAL | | | OR INDUSTRIAL PLANNED DEVELOPMENT DISTRICT SHALL NOT | | | EXCEED ONE FOOTCANDLE AT OR BEYOND THE BOUNDARIES OF | | | SUCH DEVELOPMENT." THE EXTENDED PHOTOMETRICS MUST | | | VERIFY THEY DO NOT EXCEED THIS REQUIREMENT. | | | | | | 2) NO SPEC PAGES FOR THE FIXTURES (ESPECIALLY THE | | | ROOFTOP FIXTURES) WERE PROVIDED. HOW WILL THE FIXTURES | | | KEEP GLARE FROM EXISTING THE SITE? | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | [email protected] |
|