| 2019-12-19 08:30:14 | 3RD REVIEW: 18120436 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. LIST TYPE OF GAS ON RISER, (LP OR NATURAL). |
| | |
| | 2. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, |
| | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING |
| | AND/OR SYSTEM PER THE FBC-2017 FUEL GAS APPENDIX A ? |
| | USE OF CAPACITY SECTION A.3.1(4) & 2017 FUEL GAS CODE |
| | SEC. 402.4.1. FROM THE METER TO THE NEW WATER HEATERS |
| | |
| | 3. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2017 |
| | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 |
| | PSI. SHOW ON THE RISER |
| | |
| | 4. PROVIDE THE SIZING TABLES FROM FBC FG TABLES |
| | 402.4(1-33) |
| | |
| | PREVIOUS 5. SHOW LOCATION, LENGTH, SIZE AND TERMINATION |
| | POINT OF THE GAS VENTS AND INTAKES ALSO SHOW DISTANCE |
| | FROM OTHER VENTS AND INTAKES AND ANY OPENINGS IN THE |
| | BUILDING PER FBC-2017 FUEL GAS CODE SEC. 502 THRU 505. |
| | |
| | PREVIOUS 6. THERE ARE NO SPECIFICATIONS PROVIDED PLEASE |
| | PROVIDE HEATER, PRESSURE REGULATORS AND VENTING |
| | SPECIFICATIONS FROM MANUFACTURE PER WPB AMEND TO FBC |
| | 107.2.1 |
| | TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, |
| | AND FBC-2017 FUEL GAS SEC. 402.2 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |