| 2019-03-20 14:50:48 | PLUMBING 1ST REVIEW**DENIED** |
| | |
| | 1) SHT. G175 DETAIL #4 SHOWS THE TOILET @ 1' 5" (17") |
| | TO THE CENTER. YOUR GRAB BAR IS SHOWING 6" FROM THE |
| | SIDE WALL WHICH IF THE TOILET WAS CENTERED @ 18" WOULD |
| | BE CORRECT AS THE GRAB BAR IS INSTALL 12" FROM THE |
| | CENTER LINE OF THE TOILET MEANING THIS GRAB BAR WOULD |
| | BE 5" FROM THE SIDE WALL. FBC-A 604.5.2 |
| | |
| | 2) PROVIDE ALL 3 WATER HEATER'S INSTALLATION MANUAL'S. |
| | FBC 107.2.1 |
| | |
| | 3) PROVIDE A COMPLETE ISOMETRIC OF THE NEW STORM |
| | SYSTEM. FBC 107.3.5 |
| | |
| | 4) SHT. A600 UNDER TOILET ACCESSORIES LEGEND DETAIL C |
| | AND C1 THE GRAB BAR IS LISTING AS EITHER 24", 30", OR |
| | 36". THE FLORIDA ACCESSIBILITY CODE REQUIRES THE REAR |
| | GRAB BAR TO BE MIN 36". FBC-A 604.5.2 |
| | |
| | 5) SHT.301 DOMESTIC WATER RISER DOES NOT SHOW THE |
| | REQUIRED SHUT OFF VALVE THAT SHOULD BE @ EVERY TOP-DOWN |
| | FEED IN THE PIPING SYSTEM. FBC-P 606 #5. WOULD ALSO |
| | NEED TO PROVIDE ACCESS FOR EACH VALVE. FBC-P 606.3 |
| | |
| | 6) WHAT IS THE PURPOSE OF THE DOMESTIC WATER IN THE |
| | MECH ROOM? PLEASE CLAIRFY AND DOES IT NEED BACKFLOW |
| | PROTECTION. FBC 107.2.1 |
| | |
| | 7) IT APPEARS ON THE FLAT DRAWING OF THE SANITARY |
| | SYSTEM THE FOLLOWING ROOMS HAVE THE FLOOR DRAINS DRY |
| | VENTED SO AS THE BASE OF STACK WOULD NEVER BE WASHED. |
| | BH 157, 114, 225, 159, 157, 105, 209, 218. FBC-P 912.2 |
| | |
| | 8) THERE ARE MUILT SINK DISCHARGING INTO THE BATHROOM |
| | GROUP WET VENT. ONLY THE FIXTURES OF THE BATHRROM GROUP |
| | ARE PRMITTED TO BE IN THE BATHROOM GROUP WET VENT. |
| | FBC-P 912.1. BH201, 120, 109, 107, 105, 113 |
| | |
| | 9) IT AOOEARS THE OVERALL DELELOPED LENGTH OF THE HOT |
| | WATER PIPING WILL BE OVER 50' FROM THE WATER HEATER TO |
| | THE BATHROOM GROUP BH159. |
| | |
| | 10) SHT. 100A NEAR RESTOOM BH157 HAS THE 4" SS FITTING |
| | IN THE WRONG DIRECTION. ALL FITTING SHALL BE IN THE |
| | DIRECTION OF FLOW. FBC-P 706.3 |
| | |
| | 11) A600 BATHROOM DETAIL 1-BH157PAT DOES NOT SHOW THE |
| | CLEAR FLOOR SPACE FOR THE SHOWER. FBC-A 706.3 |
| | |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | |
| | TIM HUNT |
| | PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER |
| | BUILDING DIVISION |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | [email protected] |