| 2019-03-21 08:22:08 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18120436 |
| | 3/21/19 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW SYSTEMS IN COMPLIANCE WITH SECTION C403.2.1 FBC EC. |
| | |
| | 2) PROVIDE AN ENERGY COMPLIANCE REPORT FOR THE NEW |
| | ADDITIONS- SEE SECTIONS C502.1 AND C101.5.1 FBC EC |
| | |
| | 3) COMMISSIONING OF THE MECHANICAL SYSTEMS AND |
| | ELECTRICAL LIGHTING AND POWER SYSTEMS IS REQUIRED PER |
| | SECTION C408.2 FBC-14 ENERGY CONSERVATION. SUBMIT A |
| | COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND |
| | DESCRIBED IN SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE |
| | THAT A COPY OF THE COMMISSIONING REPORT SHALL BE |
| | SUBMITTED FOR REVIEW AT FINAL INSPECTION. |
| | |
| | 4) SHEET M001: PLEASE ADD THE PRESSURE RELATIONSHIPS- |
| | POSITIVE OR NEGATIVE- FOR THE ROOMS LISTED IN THE AIR |
| | BALANCE SCHEDULES- REFER TO TABLE 7-1 DESIGN |
| | PARAMETERS, ASHRAE 170-2008. |
| | |
| | 5) M001: SOILED WORKROOMS AND SOILED HOLDING ROOMS |
| | REQUIRE A MINIMUM OF 2 OUTDOOR AIR CHANGES PER TABLE |
| | 7-1. THE SCHEDULES SHOW 0 TO BE PROVIDED. |
| | |
| | 6) M101B: FIRE DAMPERS MISSING FOR DUCTS PENETRATING |
| | THE FIRE-RATED EQUIP. STOR. RM WALLS- SECTION 607.5.2 |
| | FBC M. |
| | |
| | 7) M101A & M101B: PROVIDE EQUIPMENT SCHEDULES FOR THE |
| | APPLIANCES IN THE DINING ROOMS, AND SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS- SECTION 304.1 FBC M. |
| | |
| | 8) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS |
| | OF ALL THE ROOF TOP EQUIPM,ENT AND REQUIRED CLEARANCE |
| | DISTANCE MEASURES FOR AIR INTAKES AND ROOF EDGES- |
| | SECTION 107.2.1 WPB. |
| | |
| | 9) SUBMIT SITE SPECIFIC WIND LOAD ENGINEERING FOR TIE |
| | DOWN OF ALL ROOF MOUNTED MECHANICAL EQUIPMENT AND |
| | APPLIANCES- SECTIO N 301.15 FBC M. |
| | |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER |
| | HEATERS AND THE DRYER- SECTIONS 304.1 AND 504.1 FBC M |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |