| 2019-02-21 11:17:47 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET FP 001 - THERE ARE INDICATIONS OF FIRE |
| | SPRINKLER WORK. THERE ARE NO INDICATIONS THAT THE WORK |
| | SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS |
| | BY CERTIFIED FIRE SPRINKLER CONTRACTORS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 2) SHEET FP 101 A - THERE ARE INDICATIONS OF FIRE |
| | SPRINKLER WORK IN THE SOUTH, ADULT SECTION. THERE ARE |
| | NO INDICATIONS OF WORK IN THE NORTH, CHILD SECTION. |
| | |
| | PLEASE REVIEW AND CORRECT, AS WELL AS A NOTE OF |
| | ACKNOWLEDGEMENT FOR SEPARATE PERMITTED SHOP DRAWINGS. |
| | |
| | |
| | |
| | 3) SHEET E 001 - THERE ARE NO INDICATIONS OF FIRE ALARM |
| | DEVICES, EQUIPMENT, OR WORK OF THE FIRE ALARM SYSTEM. |
| | |
| | ANY WORK ON THE FIRE ALARM, DEMO AND/OR NEW |
| | INSTALLTIONS SHALL BE DONE UNDER SEPARATE PERMIT AND |
| | SHOP DRAWING BY CERTIFIED FIRE ALARM CONTRACTORS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 4) SHEET A 575 - THERE ARE INDICATIONS OF CARD READERS |
| | AND CONTROLLED EGRESS WITHIN THE DOOR SCHEDULE. |
| | |
| | ANY WORK OF CARD READERS AND/OR CONTROLLED EGRESS SHALL |
| | BE DONE UNDER SEPARATE SHOP DRAWINGS. |
| | |
| | ALL INSTALL INVOLVING EGRESS SHALL COMPLY WITH NFPA |
| | 101, CHAPTER 7, MEANS OF EGRESS AS APPLICABLE. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | 5) SHEET G 100 - THERE ARE NO INDICATIONS UNDER DEMO |
| | AND/OR OTHER APPLICABLE AREAS REGARDING THE LIFE SAFETY |
| | SYSTEM BEING MAINTAINED. |
| | |
| | THE FIRE SPRINKLER AND FIRE ALARM SYSTEMS SHALL BE |
| | MAINTAINED THROUGHOUT DEMO AND NEW CONSTRUCTION AT ALL |
| | TIMES. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |