| | 1ST REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | CORRECT PLANS AS NOTED BELOW PER WPB FBC 107.2.1 |
| | |
| | 1. RE: PLAN SHEET P2.1; RELOCATE FLOOR DRAIN TO COMPLY |
| | WITH FBC PL 412.2 FOR READY ACCESS. |
| | 2. RE; PLAN SHEET P0.1; PLUMBING FIXTURE SCHEDULE |
| | A) COFFEE MAKER/WATER FILTER; "PROVIDE WITH BACKFLOW |
| | PREVENTER" TO RECONCILE WITH ISOMETRIC |
| | B) DISHWASHER; |
| | 1) "CONNECT WASTE TO SINK TAILPIECE IN ACCORDANCE W/FBC |
| | PL 802.1.6" |
| | 2) "PROVIDE BACKFLOW PREVENTION AS REQUIRED BY FBC FL |
| | 409.2" |
| | C. REFRIGERATOR; "PROVIDE WITH BACKFLOW PREVENTER" TO |
| | RECONCILE WITH ISOMETRIC |
| | 3. DISHWASHER APPEARS TO BE SUPPLIED BY COLD WATER (SEE |
| | P0.1 DOMESTIC WATER ISOMETRIC AND P3.1 DOMESTIC WATER |
| | PLAN). |
| | A) PROVIDE HOT WATER PER FBC PL 607.1. |
| | B) PROVIDE WATER HAMMER ARRESTOR PER FBC PL 604.9. |
| | C) PROVIDE WATER HEATER(S) TO ADEQUATELY SUPPLY |
| | REQUIRED HOT WATER NEEDS |
| | 4. RE: P0.1 REVISE DETAIL FOR IWH DETAIL FOR PUBLIC |
| | LAVS TO ACCURATELY REFLECT THE PROJECT SITUATION PER |
| | WPB FBC 107.2.1. |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |