| Date |
Text |
| 2019-01-04 07:09:43 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE ACCURATE ONE-LINE DIAGRAM WITH WIRE SIZES |
| | AND CONDUIT SIZES TO METER-CAN, NEW ATS, GENERATOR, AND |
| | FROM ATS TO EXISTING 125AMP PANEL AND GENERATOR OCP. |
| | FBC 107.2.1 |
| | |
| | 2. PROVIDE LOAD CALCULATION SHOWING LOAD SHEDDING. NEC |
| | 220 |
| | |
| | 3. VALUE IS LOW, RAISE VALUE. VALUE TO INCLUDE ALL |
| | MATERIALS (GENERATOR INCLUDED) AND LABOR. FBC 109.3 |
| | BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| | WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 4. PLAN SHOWS 20KW GENERATOR BUT SPEC SHEETS SHOW 22KW |
| | GENERATOR. PROVIDE CLARIFICATION OF WHAT IS ACTUALLY |
| | BEING INSTALLED. FBC 107.2.1 |
| | |
| | 5. LICENSE # 13004086 IS ASSOCIATED WITH BRUCE KEMP AND |
| | DBA "DOUG'S INDUSTRIAL REFRIDGERATION INC". PLAN IS |
| | SIGNED BY LIGHTHOUSE ENERGY. ELECTRICAL PLAN MUST BE |
| | SIGNED BY ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE |
| | CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |