2018-12-12 10:26:36PERMIT # 18120390
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED WITH COMMENTS:
  
 1) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
 PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE
 OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 2) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. THE
 CLEAR PROXIMITY OF EACH TENT TO ONE ANOTHER IS NOT
 IDENTIFIED CLEARLY IN THE DRAWING. WITH EACH TENT BEING
 APPROXIMNATELY 600 SF, IT IS RECOMMENDED THAT EMERGENCY
 LIGHTING AND EXIT SIGNS BE TAKEN INTO CONSIDERATION.
  
 3) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 4) IF BEING USED, GENERATORS AND OTHER INTERNAL
 COMBUSTION POWER SOURCES SHALL BE SEPARATED FROM TENTS
 BY A MINIMUM OF 5 FEET AND SHALL BE PROTECTED FROM
 CONTACT BY FENCING OR ENCLOSURE.
  
  
  