| 2018-12-12 10:26:36 | PERMIT # 18120390 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | APPROVED WITH COMMENTS: | | | | | | 1) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | | | 2) TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. THE | | | CLEAR PROXIMITY OF EACH TENT TO ONE ANOTHER IS NOT | | | IDENTIFIED CLEARLY IN THE DRAWING. WITH EACH TENT BEING | | | APPROXIMNATELY 600 SF, IT IS RECOMMENDED THAT EMERGENCY | | | LIGHTING AND EXIT SIGNS BE TAKEN INTO CONSIDERATION. | | | | | | 3) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | 4) IF BEING USED, GENERATORS AND OTHER INTERNAL | | | COMBUSTION POWER SOURCES SHALL BE SEPARATED FROM TENTS | | | BY A MINIMUM OF 5 FEET AND SHALL BE PROTECTED FROM | | | CONTACT BY FENCING OR ENCLOSURE. | | | | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|