| 2018-12-14 10:03:36 | 1) THIS BUILDING WAS BUILT IN COMPLIANCE WITH THE |
| | FEDERAL FAIR HOUSING ACT AND THE LEVEL OF ACCESSIBILITY |
| | MUST BE MAINTAINED. A 30 INCH WIDE MINIMUM BY 48 INCH |
| | DEEP MINIMUM CLEAR FLOOR SPACE MUST BE PROVIDED |
| | ADJACENT TO THE SHOWER AND BEGINNING FLUSH WITH THE |
| | CONTROL WALL OF THE SHOWER. SHOW THE REQUIRED CLEAR |
| | FLOOR SPACE ON BOTH DRAWINGS. NO PLUMBING FIXTURES MAY |
| | ENCROACH INTO THIS CLEAR FLOOR SPACE. |
| | 2) THE EXISTING BACKING FOR FUTURE GRAB BARS SHALL NOT |
| | BE REMOVED. |
| | 3) SUBMIT MANUFACTURER'S SPCEIFICATIONS FOR THE FIRE |
| | CAULKING TO BE USED. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 4) SUBMIT DETAILS AS TO HOW THE ACRYLIC WALL SYSTEM |
| | WILL BE SECURED TO THE EXISTING TILE WALL.WPB AMEND. TO |
| | FBC SEC. 107.2.1. IF AN ADHESIVE IS TO BE USED, SUBMIT |
| | SPECIFICATIONS.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | PREFABRICATED SHOWER BASE AND WALL SYSTEM. THE UNIT |
| | SHALL COMPLY WITH 2017 FBC-PLUMBING SEC.417.1 AND ASME |
| | A112.19/CSA B45.1 OR CSA B45.5/IAPMO Z 124. |
| | 6) THE NEW SHOWER VALVE SHALL BE BALANCED PRESSURE, |
| | THERMOSTATIC, OR COMBINATION |
| | BALANCED-PRESSURE/THERMOSTATIC AND COMPLY WITH ASSE |
| | 1016/ASME A112.1016/CSA B125. 16 OR ASME A112.18.1/CSA |
| | B125.1 PER 2017 FBC PLUMBING SEC.424.3. |
| | |